VW3A3327

$585.59
Special Order-Generally ships in 14 to 21 Business Days
SKU
VW3A3327

Profinet - communication card

Main
Product or component type
Communication card
Range compatibility
Altivar 61

Altivar 71
Communication port protocol
Profinet

MRP (Media Redundancy Protocol)
Connector type
2 RJ45 connectors
Transmission rate
100 Mbits
Physical interface
RJ45 for Profinet
Web services
Data editor

Drive monitor

Drive parameters

Drive recorder

Ethernet/IP setup

Ethernet statistics

FDR Agent

Security

IPar client settings

Save/restore drive configuration

Multi-language services
Complementary
Exchange mode
Full duplex
Communication data link
LLC : IEEE 802.2

MAC : IEEE 802.3
Communication network type
Ethernet CiA 402 profile conforming to IEC 61800-7-201

Ethernet PROFIdrive profile
Communication transport type
TCP CiA 402 profile conforming to IEC 61800-7-201

UDP PROFIdrive profile

RT (real-time)
Web server
Embedded
Communication service
IPar-server

FTP
Display type
1 LED for Link (Link Status)

1 LED for MS (Module Status)

1 LED for NS (Network Status)

1 LED for TX/RX (Transmit/Receive port 1)

1 LED for TX/RX (Transmit/Receive port 2)
Product weight
0.287 kg
Offer Sustainability
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
Write Your Own Review
You're reviewing:VW3A3327

   Frequently Asked Questions and Answers


  • What supplies the power to vw3a3401 encoder interface card fitted on Altivar 71?

    The encoder interface card VW3A3401 uses an internal 5VDC supply from the drive control block. The interface card supplies 5VDC to the encoder RS422 with maximum current available up to 200mA.
    Read more

  • When does the Drive Overheat Fault (OHF) occur in Altivar 71 Drives.

    The Drive Overheat Fault (OHF) indicates that the heat sink temperature has crossed the temperature threshold. This is the information from the temperature sensor located on the heat sink, near the transistor module. When the Thermal Heat Dissipation (THD) is greater than 118% it trips in OHF. 118% is approximately 100 Deg Centigrade temperature on the heat sink. The main causes for the occurrence of this fault are: 1. Excessive ambient temperature. (Provide proper air cooling of the control roo...
    Read more

  • Altivar 61/71 what is the recommended corrective action when the motor runs in reverse with a run forward command?

    Issue: The motor is running backwards with a forward run command on the drive. Product line: Altivar ATV61 and ATV71 Environment: All models, all serial numbers Cause: The phase rotation is inverted coming out of the drive going to the motor.      Resolution: Option 1: To correct the motor rotation swap two motor leads on the drive output terminals. Option 2: Go in the simple start menu 1.1 find output phase rotation change it from ABC to ACB. Refer to the ATV61 and ATV71 programm...
    Read more

  • What does ramp increment mean for the Altivar 61/71?

    Issue:  What does ramp increment mean for the Altivar 61/71?   Product Line: Altivar 61, Altivar 71   Environment: All serial numbers   Cause: N/A   Resolution: Ramp increment is a parameter that will change the resolution of the listed parameters:  see below Inr M [Ramp increment] 0.01 - 0.1 - 1 0.1 0.01   [0.01]: Ramp up to 99.99 seconds 0.1     [0.1]: Ramp up to 999.9 seconds 1        [1]: Ramp up to 9,000 s...
    Read more

  • Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes on VFD?

    Issue:  Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes? Product Line:   Altivar 61 Altivar 71 ATV61  ATV71 Environment: All Cause: Define the No Drive Fault relay relationship with Auto restart function.  Resolution: The relay assigned to No Drive Fault will not change states on a fault, if Auto restart is set to YES, until the max restart time is depleted and the fault still exists.
    Read more

User guide
  • file image ATV61/71 PROFINET Manual - VW3A3327 (pdf) download image`
Catalogue
  • file image Catalog: Altivar 61/61 Plus variable speed drives - English version 2014/04 (web pdf format) (pdf) download image`
RoHs Declaration
  • file image Profinet - communication card (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech