3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
See link for Data Sheet:
https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7
Yes,Tesys D (LC1D*) uses linear translation movement,hence double breaking of pole is obtained,please find attached document in support of it.
The maximum DC voltage for TeSys D range contactor is 75 Volt per pole. This voltage is applicable for the specification of L/R <= 15ms in DC applications.
Issue:
Checking on the Tesys D-line relays contact ratings.
Product Line:
Tesys D Contactors
Environment:
IEC Contactors and Starters
Resolution:
The contacts are rated NEMA A600 10 amps continuous, and NEMA Q600 2.5 amps continuous.
Issue:
Will the LA4DC1U diode suppressor mount to current Tesys D DC coils?
Product Line:
IEC contactors and starters
Environment:
Products sold and used in the United States
Resolution:
No. The LA4DC1U diode unit will only fit the older TeSys D contactors. Tesys D DC coils include suppression automatically, it`s not needed.