Issue User is trying to purchase a cable to wire serial communication to EGX150 (Link150) to downstream devices through its RJ45 serial port Product Line EGX150 (Link150) Environment Serial communication Resolution Part# VW3A8306d30 This cable is for Modbus serial link 1xRJ45, free wires at the other end. 3m length The correspondence between the wire colors of cable VW3A8306D30 and the pin numbers of the RJ45 socket is as follows:
Read more
Issue Documentation for egx150 or link150 .
Read more
Issue The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector. Product Line Link150, EGX150 Environment EGX150 serial connections Cause The EGX150 does not use the standard RS-485 connector. Resolution Pin Number Colour Signal name Description 1 Orange/White striped Rx- Receive Data - 2 Orange Rx+ Receive Data + 3 NC No Connection 4 Blue Tx+ Transmit Data + 5 Blue/white striped Tx- Transmit Data - 6 NC No Connect...
Read more
Issue EGX150 used as a master device that is connected to downstream devices such as a CM2000 Product Line EGX150 (Link150), CM2000 Series Environment Communications, Wiring, Gateway Supported device type Resolution The EGX150 does have the capability of having a CM2000 series as a downstream device. The protocol on the EGX150 must be set to PowerLogic (SY/MAX) in order for a connection to be established. CM2000 series meters are not designed to do 2 wire RS-485 communication. CM2000 series meters can ...
Read more
Issue: Need to find the default IP address for the Link150 (EGX15) Ethernet Gateway Product Line: Link150 Ethernet Gateway (EGX150) Environment: Link150 Webpage Connection (EGX150) Cause: Unable to connect to the Link150 Ethernet Gateway (EGX150) Resolution: The default IP address for the Ethernet Gateway Link150 (EGX150) is 169.254.YY.ZZ YY.ZZ are the last 2 bytes of the Link150 MAC address. For example, A Link150 with MAC address 00-B0-D0-86-BB-F7 (hexadecimal) or 0-176-208-134-187-247 (decimal...
Read more