XPSVNE3742HSP

$1,430.29
Special Order-Generally ships in 14 to 21 Business Days
SKU
XPSVNE3742HSP

module XPSVN - zero speed detection - 230 V DC for motor power supply > 60 Hz

Main
Range of product
Preventa Safety automation
Product or component type
Preventa safety module
Safety module name
XPSVNE
Safety module application
For zero speed detection
Function of module
Monitoring 3-phase motor with variable number of poles and star-delta starting

Monitoring 3-phase motor + variable speed drive

Monitoring 3-phase motor with star-delta starting

Monitoring 3-phase motor

Monitoring dc motor

Monitoring XPS AK

Monitoring star-delta motor starter and guard switch type XCS E
Safety level
Can reach PL d/category 3 conforming to EN/ISO 13849-1

Can reach SILCL 2 conforming to EN/IEC 62061
Safety reliability data
MTTFd = 124.1 years conforming to EN/ISO 13849-1

DC > 99 % conforming to EN/ISO 13849-1

PFHd = 9.26E-9 1/h conforming to EN/IEC 62061
[Us] rated supply voltage
230 V AC (- 15...10 %)
Output type
Relay 1 NO + 1 NC, volt-free
Number of additional circuits
2 solid state outputs
Complementary
Product destination
For motor power supply > 60 Hz
Power consumption in VA
<= 7 VA
Input voltage
500 Vrms
Input detection threshold
0.01...0.1 V
Breaking capacity
C300 : holding 180 VA AC-15 for relay output

C300 : inrush 1800 VA AC-15 for relay output
Breaking capacity
10 mA / 48 V for solid state output circuit

20 mA / 24 V for solid state output circuit

1.5 A / 24 V - L/R = 50 ms, DC-13 for NO relay output circuit

1.2 A / 24 V - L/R = 50 ms, DC-13 for NC relay output circuit
[Ith] conventional free air thermal current
<= 2.5 A for relay output
Associated fuse rating
4 A gG for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Minimum output current
10 mA for relay output
Minimum output voltage
17 V for relay output
[Ui] rated insulation voltage
300 V, degree of pollution 2 conforming to IEC 60947-5-1

300 V, degree of pollution 2 conforming to DIN VDE 0110 parts 1 and 2
[Uimp] rated impulse withstand voltage
4 kV overvoltage category III, conforming to IEC 60947-5-1

4 kV overvoltage category III, conforming to DIN VDE 0110 parts 1 and 2
Local signalling
4 LEDs
Connections - terminals
Captive screw clamp terminals, removable terminal block flexible cable : 0.2...1.5 mm² without cable end, 2 wires

Captive screw clamp terminals, removable terminal block flexible cable : 0.2...2.5 mm² without cable end, 1 wire

Captive screw clamp terminals, removable terminal block flexible cable : 0.25...1 mm² with cable end, without bezel, 2 wires

Captive screw clamp terminals, removable terminal block flexible cable : 0.25...2.5 mm² with cable end, with bezel, 1 wire

Captive screw clamp terminals, removable terminal block flexible cable : 0.25...2.5 mm² with cable end, without bezel, 1 wire

Captive screw clamp terminals, removable terminal block flexible cable : 0.5...1.5 mm² with cable end, with double bezel, 2 wires

Captive screw clamp terminals, removable terminal block solid cable : 0.2...1 mm² without cable end, 2 wires

Captive screw clamp terminals, removable terminal block solid cable : 0.2...2.5 mm² without cable end, 1 wire
Mounting support
35 mm symmetrical DIN rail
Depth
114 mm
Height
99 mm
Width
45 mm
Product weight
0.6 kg
Environment
Standards
EN/IEC 60204-1

EN/IEC 60947-5-1
Product certifications
CSA

TÜV

UL
IP degree of protection
IP20(terminals) conforming to EN/IEC 60529

IP40(enclosure) conforming to EN/IEC 60529
Ambient air temperature for operation
-10...55 °C
Ambient air temperature for storage
-25...85 °C
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:XPSVNE3742HSP

   Frequently Asked Questions and Answers


  • Compatible Preventa XPS safety modules for the xcsdm379110 coded magnetic safety switch

    Which Preventa XPS safety modules are compatible with the  XCSDM379110 coded magnetic safety switch? The information is in the attached file named \'XCSDM37_possible associations to XPS units_V4 feb 2015\' This information is subject to being changed without notification. XCSDM37_possible associations to XPS units_V4 feb 2015.pdf
    Read more

  • Preventa XU_User manual of the xpslcm1150 muting relay

    Please find attached the user manual of the XPSLCM1150 muting relay able to monitor 2 safety light curtains. XPSLCM1150 user manual En_170634802a55.pdf
    Read more

  • Preventa XU_Catalogue pages of the xpslcm1150 muting relay for type 2 and type 4 safety light curtains

    Please find attached the catalogue pages of the XPSLCM1150 muting relay for type 2 and type 4 safety light curtains 30311-en_XPSLCM1150 catalog pages.pdf
    Read more

  • Preventa XU_Recommended muting lamps to associate with the xpslcmut1160 muting relay for type 4 or type 2 light curtain

    Please find attached a document giving all the tested beacons in the association with the XPSLCMUT1160 muting relay for type 4 or type 2 light curtain. Led beacons are proposed. XPSLCMUT1160 muting relay_Muting light VF.pdf
    Read more

  • Replacement for XPSECP5131

    Issue: Replacement for the XPSECP5131 Product Line: Preventa XPS Resolution: The replacement for the XPSECP5131 is the use XPSECPE5131P
    Read more

Catalogue
  • file image Preventa safety modules XPSVNE For zero speed detection (pdf) download image`
Certificate
  • file image XPSVNE Type Examination (pdf) download image`
  • file image CCC Certificate XPS type AC AF AFL AK (pdf) download image`
Declaration of conformity
  • file image Preventa DoC VNE (pdf) download image`
End of life manual
  • file image XPS ABV..., XPS AC..., XPS AF..., XPS AX..., XPS BCE..., XPS BF..., XPS DMB..., XPS ECME..., XPS-VC... Safety Modules, Product End-of-Life Instructions (pdf) download image`
  • file image XPS... Preventa Safety Module, Product End-of-Life Instructions (pdf) download image`
Product environmental
  • file image XPS... Preventa Safety Module, Product Environmental Profile (pdf) download image`

Dimensions Drawings

Dimensions





© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech