VW3A8306RC

$53.76
Generally ships in 1 to 2 days
SKU
VW3A8306RC

Modbus line terminator - for end of RS485 line - RJ45 connector

Main
Range of product
Altivar
Bus type
Modbus
Accessory / separate part category
Connection accessory
Accessory / separate part type
Line terminator
Accessory / separate part destination
RJ45 connector
Quantity per set
Set of 2
Complementary
Range compatibility
Altivar Machine ATV340 except Sercos drives

Altivar Machine ATV320

Altivar Process ATV900

Altivar 32

Altivar Easy 610

Altivar Process ATV600

Altivar 71Q

Altivar 71

Altivar 61Q

Altivar 61

Zelio Logic

Altivar 31

Preventa XPS MF

Modicon M258

Modicon LMC058

Altistart 48

Altivar 12

Altivar 212

Modicon M238

Altivar 21

Altistart 22

Lexium SD3

Altivar 31C

Altivar Easy 310

Altivar 312
Communication port protocol
Modbus
Terminator resistance
120 Ohm
Terminator capacitance
1 nF
Product weight
0.2 kg
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:VW3A8306RC

   Frequently Asked Questions and Answers


  • What supplies the power to vw3a3401 encoder interface card fitted on Altivar 71?

    The encoder interface card VW3A3401 uses an internal 5VDC supply from the drive control block. The interface card supplies 5VDC to the encoder RS422 with maximum current available up to 200mA.
    Read more

  • When does the Drive Overheat Fault (OHF) occur in Altivar 71 Drives.

    The Drive Overheat Fault (OHF) indicates that the heat sink temperature has crossed the temperature threshold. This is the information from the temperature sensor located on the heat sink, near the transistor module. When the Thermal Heat Dissipation (THD) is greater than 118% it trips in OHF. 118% is approximately 100 Deg Centigrade temperature on the heat sink. The main causes for the occurrence of this fault are: 1. Excessive ambient temperature. (Provide proper air cooling of the control roo...
    Read more

  • Altivar 61/71 what is the recommended corrective action when the motor runs in reverse with a run forward command?

    Issue: The motor is running backwards with a forward run command on the drive. Product line: Altivar ATV61 and ATV71 Environment: All models, all serial numbers Cause: The phase rotation is inverted coming out of the drive going to the motor.      Resolution: Option 1: To correct the motor rotation swap two motor leads on the drive output terminals. Option 2: Go in the simple start menu 1.1 find output phase rotation change it from ABC to ACB. Refer to the ATV61 and ATV71 programm...
    Read more

  • What does ramp increment mean for the Altivar 61/71?

    Issue:  What does ramp increment mean for the Altivar 61/71?   Product Line: Altivar 61, Altivar 71   Environment: All serial numbers   Cause: N/A   Resolution: Ramp increment is a parameter that will change the resolution of the listed parameters:  see below Inr M [Ramp increment] 0.01 - 0.1 - 1 0.1 0.01   [0.01]: Ramp up to 99.99 seconds 0.1     [0.1]: Ramp up to 999.9 seconds 1        [1]: Ramp up to 9,000 s...
    Read more

  • Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes on VFD?

    Issue:  Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes? Product Line:   Altivar 61 Altivar 71 ATV61  ATV71 Environment: All Cause: Define the No Drive Fault relay relationship with Auto restart function.  Resolution: The relay assigned to No Drive Fault will not change states on a fault, if Auto restart is set to YES, until the max restart time is depleted and the fault still exists.
    Read more

User guide
  • file image ULP System for Masterpact and Compact - User Guide (EN) (pdf) download image`
  • file image ULP System for Masterpact and PowerPact - User Guide (EN) (pdf) download image`
Catalogue
  • file image Altivar 312 variable speed drives catalogue (pdf) download image`
  • file image Altivar 212 variable drives 2011/03 (web PDF format) (pdf) download image`
  • file image Smart Relays - Zelio Logic (pdf) download image`
  • file image Catalog: Altivar 71/71 Plus variable speed drives - English version 2014/04 (web pdf format) (pdf) download image`
  • file image Catalog: Altivar 61/61 Plus variable speed drives - English version 2014/04 (web pdf format) (pdf) download image`
  • file image Catalog: Soft start/soft stop units Altistart 22 (pdf) download image`
  • file image Catalogue Modicon M340 automation platform - English version 2014/09 (web pdf format) (pdf) download image`
  • file image Catalog: Soft start/soft stop units Altistart 48 (pdf) download image`
  • file image Altivar 12 Catalogue EN_Ed 2015-01 (Low resolution PDF) (pdf) download image`
  • file image Catalog: Altivar 32 variable speed drives (pdf) download image`
  • file image Modbus for machines with Modicon logic controllers (pdf) download image`
  • file image Modicon M221 logic controllers (pdf) download image`
  • file image Altivar Machine ATV320 variable speed drives - Catalog (pdf) download image`
  • file image Modicon M251 logic controllers (pdf) download image`
  • file image Catalog: Altivar Process ATV600 variable speed drives - English version 2018/05 (pdf) (pdf) download image`
Catalogue Page
  • file image Variable speed drives ATV 312 (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech