line choke - 0.155 mH - 184 A - 3 phases - 220 W - for variable speed drive

Main
Range of product
Altivar
Product or component type
Line choke
Product compatibility
ATV61HD90N4D - line choke - 1 per drive

ATV61WD90N4 - line choke - 1 per drive

ATV61WD90N4C - line choke - 1 per drive

ATV71HD75N4 - line choke - 1 per drive

ATV71WD75N4 - line choke - 1 per drive
Network number of phases
Three phase
Range compatibility
Altivar 61

Altivar 71
Device application
Reduction of current harmonics
Value of inductance
0.155 mH
[In] rated current
184 A
Saturation current
370 A
Thermal losses
220 W
Electrical connection
Bare wires, Ø = 9 mm
Complementary
Supply frequency
50...60 Hz
Max current
1.65 x nominal current for 60 s
Voltage drop at rated load
5 %
Electrical insulation class
Class F
Clearance distance
5.5 mm conforming to IEC 60664
Leakage distance
11.5 mm conforming to IEC 60664
Product weight
31 kg
Width
280 mm
Height
330 mm
Depth
210 mm
Environment
Standards
EN 50178

IEC 60076 (with HD398)

VDE 0160 level 1
IP degree of protection
IP00 (choke)

IP00 (terminals)
Environmental characteristic
3B1 conforming to IEC 721-3-3

3C2 conforming to IEC 721-3-3

3S1 conforming to IEC 721-3-3
Pollution degree
2 conforming to EN 50178
Vibration resistance
1.5 mm peak to peak (f = 3...13 Hz) conforming to IEC 60068-2-6

1 gn (f = 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
0...95 %
Ambient air temperature for operation
> 45...< 55 °C with current derating of 2 % per °C

0...45 °C without current derating
Ambient air temperature for storage
-25...70 °C
Operating altitude
1000...3000 m with current derating 1 % per 100 m
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:VW3A4558

   Frequently Asked Questions and Answers


  • What supplies the power to vw3a3401 encoder interface card fitted on Altivar 71?

    The encoder interface card VW3A3401 uses an internal 5VDC supply from the drive control block. The interface card supplies 5VDC to the encoder RS422 with maximum current available up to 200mA.
    Read more

  • When does the Drive Overheat Fault (OHF) occur in Altivar 71 Drives.

    The Drive Overheat Fault (OHF) indicates that the heat sink temperature has crossed the temperature threshold. This is the information from the temperature sensor located on the heat sink, near the transistor module. When the Thermal Heat Dissipation (THD) is greater than 118% it trips in OHF. 118% is approximately 100 Deg Centigrade temperature on the heat sink. The main causes for the occurrence of this fault are: 1. Excessive ambient temperature. (Provide proper air cooling of the control roo...
    Read more

  • Altivar 61/71 what is the recommended corrective action when the motor runs in reverse with a run forward command?

    Issue: The motor is running backwards with a forward run command on the drive. Product line: Altivar ATV61 and ATV71 Environment: All models, all serial numbers Cause: The phase rotation is inverted coming out of the drive going to the motor.      Resolution: Option 1: To correct the motor rotation swap two motor leads on the drive output terminals. Option 2: Go in the simple start menu 1.1 find output phase rotation change it from ABC to ACB. Refer to the ATV61 and ATV71 programm...
    Read more

  • What does ramp increment mean for the Altivar 61/71?

    Issue:  What does ramp increment mean for the Altivar 61/71?   Product Line: Altivar 61, Altivar 71   Environment: All serial numbers   Cause: N/A   Resolution: Ramp increment is a parameter that will change the resolution of the listed parameters:  see below Inr M [Ramp increment] 0.01 - 0.1 - 1 0.1 0.01   [0.01]: Ramp up to 99.99 seconds 0.1     [0.1]: Ramp up to 999.9 seconds 1        [1]: Ramp up to 9,000 s...
    Read more

  • Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes on VFD?

    Issue:  Will the relay output, assigned to No Drive Fault, change states on a fault if Auto restart is set to yes? Product Line:   Altivar 61 Altivar 71 ATV61  ATV71 Environment: All Cause: Define the No Drive Fault relay relationship with Auto restart function.  Resolution: The relay assigned to No Drive Fault will not change states on a fault, if Auto restart is set to YES, until the max restart time is depleted and the fault still exists.
    Read more

Catalogue
  • file image Catalog: Altivar 71/71 Plus variable speed drives - English version 2014/04 (web pdf format) (pdf) download image`
  • file image Catalog: Altivar 61/61 Plus variable speed drives - English version 2014/04 (web pdf format) (pdf) download image`
Instruction sheet
  • file image Instruction sheet - Line & motor choke 3 phases - VW3A4551-572 (pdf) download image`
CAD
  • file image AC line choke 155µH 184A (dwf) download image`
  • file image AC line choke 155µH 184A (dwg) download image`
  • file image AC line choke 155µH 184A (dxf) download image`
  • file image AC line choke 155µH 184A (wmf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech