There is no input to select between direct/inverse direction at the PID function block from the Util library. The FB_PID function block (Toolbox library) is from Schneider and has additional features. With FB_PID function block from the Toolbox library in SoMachine to change the regulation direction user can use negative P-factor (i_rKp) The basic PID function must remain the same.
Read more
There is no issue to use 800 series IOs without any impact on TÜV certificate on a M580 Safety configuration. As a general rule, all of Remote Distributed equipments on Ethernet allowed in M580 system could be considered as “non-interfering” for Safety M580 modules. However, of course, 800 series IOs data are not supposed to be used to perform safety functions.
Read more
The video demonstrates how to set up persistent variables and save them in the memory words of SoMachine Basic.
Read more
The attached video will illustrate creating 3 IODDTs for an M340 IO module: One for the Module health itself. One for Channel 0 using T_DIS_OUT_GEN which has two components. One for Channel 1 using T_DIS_OUT_STD which has 22 components.
Read more
N° | Profibus |
---|---|
1 | Shield |
2 | Output ground 24 V |
3 | RXD-TXD + |
4 | Repeater Control Signal TRS |
5 | Ground 0 V |
6 | 5 V |
7 | 24 V |
8 | RXD-TXD- |
9 | Control Signal direction |
*Shield: To be connected externally to the protective earth