The replacement is the STBDDO3600K. The \'K\' at the end of the part number designates kit. The kit now contains module, base and appropriate number of both spring and screw type connectors.
Read more
For proper heat dissipation, allow a minimum clearance of 100mm (3.94in.) above and below each island segment.
Read more
No. All of the Advantys input modules are sink modules. Legacy KB System (APS) Data: RESL212843 V1.0, Originally authored by DiSa on 10/23/2013, Last Edited by DiSa on 10/23/2013 Related ranges: Modicon STB
Read more
No, there are no 24 volt DC true low modules available for Advantys. Legacy KB System (APS) Data: RESL174065 V4.0, Originally authored by MiRo on 11/15/2007, Last Edited by DaSo on 11/28/2012 Related ranges: Modicon STB
Read more
No, the removable memory card is optional since the NIMs have flash memory. When the configuration software is not used and the system is auto-configured, the configuration is saved to flash only. To use the removable SIM card, the configuration software is required and an action to Save to the SIM card has to be performed while online.
Read more
6 two-wire actuators
Pin | Top Connector | Bottom Connector |
---|---|---|
1 | output to actuator 1 | output to actuator 4 |
2 | field power return | field power return |
3 | output to actuator 2 | output to actuator 5 |
4 | field power return | field power return |
5 | output to actuator 3 | output to actuator 6 |
6 | field power return | field power return |