SR3XT61FU

$170.51
Special Order-Generally ships in 14 to 21 Business Days
SKU
SR3XT61FU

discrete I/O extension module - 6 I O - 100..240 V AC - for Zelio Logic

Main
Range of product
Zelio Logic
Product or component type
Discrete I/O extension module
Complementary
Number or control scheme lines
120 with ladder programming
Cycle time
6...90 ms
Backup time
10 years at 25 °C
Clock drift
12 min/year at 0...55 °C
Checks
Program memory on each power up
[Us] rated supply voltage
100...240 V AC
Supply voltage limits
85...264 V
Supply frequency
50/60 Hz
Reverse polarity protection
With
Discrete input number
4
Discrete input voltage
100...240 V AC
Discrete input current
0.6 mA
Discrete input frequency
47...53 Hz

57...63 Hz
Voltage state 1 guaranteed
>= 79 V for discrete input
Voltage state 0 guaranteed
<= 40 V for discrete input
Current state 1 guaranteed
>= 0.17 mA for discrete input
Current state 0 guaranteed
<= 0.5 mA for discrete input
Input impedance
350 kOhm (discrete input)
Number of outputs
2 relay output(s)
Output voltage limits
24...250 V AC

5...30 V DC (relay output)
Contacts type and composition
NO for relay output
Output thermal current
8 A for all 2 outputs (relay output)
Electrical durability
500000 cycles at 230 V, 0.9 A (AC-15) for relay output conforming to EN/IEC 60947-5-1

500000 cycles at 230 V, 1.5 A (AC-12) for relay output conforming to EN/IEC 60947-5-1

500000 cycles at 24 V, 0.6 A (DC-13) for relay output conforming to EN/IEC 60947-5-1

500000 cycles at 24 V, 1.5 A (DC-12) for relay output conforming to EN/IEC 60947-5-1
Switching capacity in mA
>= 10 mA at 12 V (relay output)
Operating rate in Hz
0.1 Hz (at Ie) for relay output

10 Hz (no load) for relay output
Mechanical durability
10000000 cycles (relay output)
[Uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
Response time
10 ms (from state 0 to state 1) for relay output

5 ms (from state 1 to state 0) for relay output

50 ms with ladder programming (from state 0 to state 1) for discrete input

50 ms with ladder programming (from state 1 to state 0) for discrete input

50...255 ms with FBD programming (from state 0 to state 1) for discrete input

50...255 ms with FBD programming (from state 1 to state 0) for discrete input
Connections - terminals
Screw terminals, flexible cable with cable end 1 x 0.25...1 x 2.5 mm² / AWG 24...AWG 14 AWG

Screw terminals, flexible cable with cable end 2 x 0.25...2 x 0.75 mm² / AWG 24...AWG 18 AWG

Screw terminals, semi-solid cable 1 x 0.2...1 x 2.5 mm² / AWG 25...AWG 14 AWG

Screw terminals, solid cable 1 x 0.2...1 x 2.5 mm² / AWG 25...AWG 14 AWG

Screw terminals, solid cable 2 x 0.2...2 x 1.5 mm² / AWG 24...AWG 16 AWG
Tightening torque
0.5 N.m
Overvoltage category
III conforming to EN/IEC 60664-1
Product weight
0.125 kg
Environment
Product certifications
CSA

C-Tick

GL

GOST

UL
Standards
EN/IEC 60068-2-27 Ea

EN/IEC 60068-2-6 Fc

EN/IEC 61000-4-11

EN/IEC 61000-4-12

EN/IEC 61000-4-2 level 3

EN/IEC 61000-4-3

EN/IEC 61000-4-4 level 3

EN/IEC 61000-4-5

EN/IEC 61000-4-6 level 3
IP degree of protection
IP20 (terminal block) conforming to IEC 60529

IP40 (front panel) conforming to IEC 60529
Environmental characteristic
EMC directive conforming to EN/IEC 61000-6-2

EMC directive conforming to EN/IEC 61000-6-3

EMC directive conforming to EN/IEC 61000-6-4

EMC directive conforming to EN/IEC 61131-2 zone B

Low voltage directive conforming to EN/IEC 61131-2
Disturbance radiated/conducted
Class B conforming to EN 55022-11 group 1
Pollution degree
2 conforming to EN/IEC 61131-2
Ambient air temperature for operation
-20...40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2

-20...55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Ambient air temperature for storage
-40...70 °C
Operating altitude
2000 m
Altitude transport
<= 3048 m
Relative humidity
95 % without condensation or dripping water
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:SR3XT61FU

   Frequently Asked Questions and Answers


  • Video: How do you create a programmed Zelio, Memory Module for a SR2/SR3 blind unit?

    Issue: How do you create a programmed Zelio, Memory Module for a SR2/SR3 blind unit? Product Line: Zelio Logic Smart Relays Environment: SR2 Compact and SR3 Modular Relays Cause: Clarification on programming and installation.                     Resolution:                          &nb...
    Read more

  • Do Zelio Logic relays include software?

    Issue: Do Zelio Logic relays include software? Product Line: Logic relays Environment: Zelio Logic Cause: Product Features Resolution: Zelio soft Software is sold as a separate accessory: SR2SFT01. This can also be downloaded at no charge at  https://www.schneider-electric.com/download/ww/en/results/3541958-SoftwareFirmware/0/8336552-Zelio-Logic/0/?showAsIframe=false CTA-ID : 2025929
    Read more

  • Why does the Zelio Logic Relays turn automatically off.

    One of the main reasons for the Zelio Logic Relays turning off automatically is input supply voltage fluctuation. The voltage limit for Zelio Logic Relays like SR2 B121JD, SR2 B201JD and SR3 B261JD, with standard input voltage 12V DC, is  10.4 VDC to 14.4 VDC. The Zelio Logic Relays work properly within the band 10.4 VDC to 14.4 VDC. The moment the input voltage either falls below the lower limit (10.4 VDC) or goes above upper limi...
    Read more

  • What is the life span of the internal lithium battery of Zelio Logic Relays

    The life span of the internal lithium battery of Zelio Logic Relays is 10 years for temperature between -20 to 50 Degree Celsius and is counted from the date of manufacturing. 
    Read more

  • How to establish bluetooth communication for SR2/SR3 range of Zelio Logic Smart Relay.

    Bluetooth interface SR2BTC01 and Bluetooth Modbus Adapter VW3A8115 can be used for establishing wireless bluetooth communication between SR2/SR3 Zelio Logic Smart Relay and computer.Note:1. The maximum distance between the computer and the module with bluetooth interface is approximately 10 meters.2. The bluetooth interface SR2CBT01 is compatible with ZelioSoft2 V4.1 and higher.3. Also It is necessary to have a SR2/SR3 Zelio Logic Smart Relay with a firmware version V4.0 and higher.The User Manu...
    Read more

User guide
  • file image Zelio Logic 2 Quick Start (pdf) download image`
  • file image Zelio Logic - Smart Relay, User Manual (pdf) download image`
  • file image Zelio Logic Programming Guide (pdf) download image`
  • file image Zelio Soft 2, Applications Examples Guide (pdf) download image`
Catalogue
  • file image Smart Relays - Zelio Logic (pdf) download image`
Instruction sheet
  • file image SR3XT... Zelio Logic 2 expansion modules (pdf) download image`
CAD
  • file image I/O extension modules 24 V DC or 24 V AC or 100 to 240 V AC (dwf) download image`
  • file image I/O extension modules 24 V DC or 24 V AC or 100 to 240 V AC (dwg) download image`
  • file image I/O extension modules 24 V DC or 24 V AC or 100 to 240 V AC (dxf) download image`
  • file image I/O extension modules 24 V DC or 24 V AC or 100 to 240 V AC (wmf) download image`
Certificate
  • file image RCM_SR2_SR3_Zelio_Relay (pdf) download image`
Declaration of conformity
  • file image EC_Declaration_SR2_SR3 (pdf) download image`
End of life manual
  • file image Zelio Logic SR2 - SR3 Smart Relays, Product End-of-Life Instructions (pdf) download image`
  • file image SR3 NET01BD, SR3 XT..., SR3 MBU01BD Network communication and I/O extension modules, Product End-of-Life Instructions (pdf) download image`
Marine certificate
  • file image DNV-GL Marine Certificate Zelio SR2 SR3 Smart Relays (pdf) download image`
Product environmental
  • file image Zelio Logic SR2 - SR3 Smart Relays, Product Environmental Profile (pdf) download image`

Dimensions Drawings

I/O Extension Modules
Mounting on 35 mm/1.38 in. DIN Rail



Screw Fixing (Retractable Lugs)



SR3

a (mm/in.)

G (mm/in.)

XT61••

35 / 1.38

25 / 0.98

XT101••

72 / 2.83

60 / 2.36

XT141••

72 / 2.83

60 / 2.36



Connections and Schema

Connection of Smart Relays on AC Supply
SR••••1B, SR••••1FU



(1)
1 A quick-blow fuse or circuit-breaker.
(2)
Fuse or circuit-breaker.
(3)
Inductive load.
(4)
Q9 and QA: 5 A (max. current in terminal C: 10 A).
With Discrete I/O Extension Module

SR3B•••B + SR3XT•••B, SR3B•••FU + SR3XT•••FU



(1)
1 A quick-blow fuse or circuit-breaker.

NOTE: QF and QG: 5 A for SR3XT141••



Performance Curves

Compact and Modular Smart Relays
Electrical Durability of Relay Outputs

(in millions of operating cycles, conforming to IEC/EN 60947-5-1)

AC-12 (1)



X:
Current (A)
Y:
Millions of operating cycles
(1)
AC-12: switching resistive loads and opto-coupler isolated solid-state loads, cos ≥ 0.9.

AC-14 (1)



X:
Current (A)
Y:
Millions of operating cycles
(1)
AC-14: switching small electromagnetic loads ≤ 72 VA, make: cos = 0.3, break: cos = 0.3.

AC-15 (1)



X:
Current (A)
Y:
Millions of operating cycles
(1)
AC-15: switching electromagnetic loads ≥ 72 VA, make: cos = 0.7, break: cos = 0.4.


© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech