After power-up, pulsing or maintaining of control contact Y1 starts the timing T.
At the end of this timing period T, the output R closes.
The output relay will be reset the next time control contact Y1 is pulsed or maintained.
After power-up, pulsing or maintaining of control contact Y1 starts the timing T. A single cycle then starts with 2 timing periods T of equal duration (start with output in rest position).
Output relay closes at the end of the first timing period T and reverts to its initial position at the end of the second timing period T.
Control contact Y1 must be reset in order to re-start the single flashing cycle.
After power-up and an initial control pulse C, the output relay closes.
If the interval between two control pulses C is greater than the set timing period T, timing elapses normally and the output relay closes at the end of the timing period. If the interval is not greater than the set timing period, the output relay remains closed until this condition is met.
An initial timing period T begins on energization. At the end of this timing period, the output relay closes.
As soon as there is a control pulse C, the output relay reverts to its initial state until the interval between two control pulses is less than the value of the set timing period T. Otherwise, the output relay closes at the end of the timing period T.
The timing period T begins on energization.
At the end of this period, the output relay closes for a fixed time P.
On energization, timing period T starts (it can be interrupted by operating the Gate control contact G).
At the end of this period, the output relay closes for a fixed time P.
T = t1+t2 P = 500ms
After power-up, pulsing or maintaining of control contact Y1 switches the output on.
A second pulse on the control contact Y1 switches the output relay off.
After power-up, pulsing or maintaining of control contact Y1 switches output relay on and starts timing T.
The output switches off at the end of the timing period T or following a second pulse on the control contact Y1.
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
After power-up and opening of the control contact, the output(s) close(s) for a timing period T.
At the end of this timing period the output(s) revert(s) to its/their initial state.
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
Relay de-energised
Relay energised
Output open
Output closed
Control contact
2 timed outputs
The second output is instantaneous if the right position is selected
Timing period
Supply