RE17RCMU
off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC
SKU
RE17RCMU
$162.58
Catalogue
Instruction sheet
Certificate
Declaration of conformity
End of life manual
REACh Declaration
RoHs Declaration
off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC
device short name | RE17R |
---|---|
width | 17.5 mm |
power supply voltage | 24 V, 24...240 V |
[Us] rated supply voltage | 24 V, 24...240 V |
time delay type | C |
Write Your Own Review
Main
- Range of product
- Zelio Time
- Product or component type
- Modular timing relay
- Discrete output type
- Relay
- Width
- 17.5 mm
- Device short name
- RE17R
- Time delay type
- C
- Time delay range
- 0.1...1 s
1...10 h
1...10 min
1...10 s
10...100 h
6...60 min
6...60 s - Nominal output current
- 8 A
Complementary
- Contacts type and composition
- 1 C/O
- Contacts material
- Cadmium free
- Control type
- Selector switch on front panel
- [Us] rated supply voltage
- 24...240 V AC at 50/60 Hz
24 V DC - Voltage range
- 0.85...1.1 Us
- Supply frequency
- 50...60 Hz (+/- 5 %)
- Input voltage
- 10 V
- Connections - terminals
- Screw terminals, clamping capacity: 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12 (solid) without cable end
Screw terminals, clamping capacity: 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14 (solid) without cable end
Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14 (flexible) with cable end
Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (flexible) with cable end - Tightening torque
- 0.6...1 N.m conforming to IEC 60947-1
- Housing material
- Self-extinguishing
- Repeat accuracy
- +/- 0.5 % conforming to IEC 61812-1
- Temperature drift
- +/- 0.05 %/°C
- Voltage drift
- +/- 0.2 %/V
- Setting accuracy of time delay
- +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
- Impulse duration
- 100 ms with load in parallel typical
30 ms typical - Insulation resistance
- 100 MOhm at 500 V DC conforming to IEC 60664-1
- Reset time
- 120 ms on de-energisation typical
- On-load factor
- 100 %
- Power consumption in VA
- 0...32 VA at 240 V AC
- Power consumption in W
- <= 0.6 W at 24 V DC
- Minimum switching current
- 10 mA at 5 V DC
- Maximum switching current
- 8 A AC/DC
- Maximum switching voltage
- 250 V AC
- Breaking capacity
- <= 2000 VA
- Operating rate in Hz
- 10 Hz
- Electrical durability
- 100000 cycles for resistive load (8 A at 250 V AC maximum)
- Mechanical durability
- 10000000 cycles
- Dielectric strength
- 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
- [Uimp] rated impulse withstand voltage
- 5 kV (1.2/50 µs)
- Delay response
- < 100 ms
- Marking
- CE
- Creepage distance
- 4 kV/3 conforming to IEC 60664-1
- Safety reliability data
- MTTFd = 296.8 years
B10d = 270000 - Mounting position
- Any position in relation to normal vertical mounting plane
- Mounting support
- 35 mm DIN rail conforming to EN/IEC 60715
- Local signalling
- LED indicator on steady: relay energised, no timing in progress
LED indicator flashing: timing in progress (80 % ON and 20 % OFF)
LED indicator pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) (5 % ON and 95 % OFF) - Product weight
- 0.07 kg
Environment
- Immunity to microbreaks
- <= 20 ms
- Standards
- 2004/108/EC
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
IEC 61812-1
2006/95/EC - Product certifications
- CSA
cULus
GL - Ambient air temperature for storage
- -30...60 °C
- Ambient air temperature for operation
- -20...60 °C
- IP degree of protection
- IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529 - Vibration resistance
- 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
- Shock resistance
- 15 gn (duration = 11 ms) conforming to IEC 60068-2-27
- Relative humidity
- 93 % without condensation conforming to IEC 60068-2-30
- Electromagnetic compatibility
- Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3 level 3
Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC 61000-4-4 level 3
Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
Conducted RF disturbances, 0.15...80 MHz at 10 V conforming to IEC 61000-4-6 level 3
Voltage dips and interruptions immunity test, 1 cycle at 0 % conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test, 25/30 cycles at 70 % conforming to IEC 61000-4-11
Conducted and radiated emissions conforming to EN 55022 class B
Offer Sustainability
- Sustainable offer status
- Green Premium product
- RoHS (date code: YYWW)
- Schneider Electric declaration of conformity
- REACh
- Reference not containing SVHC above the threshold
- Product environmental profile
- End of Life Information
- Product end of life instructions
- Available