LV433650
circuit breaker Compact NSX400HB2 - Micrologic 6.3 E-M - 320 A - 3 poles 3d
SKU
LV433650
$9,865.24
User guide
Catalogue
Instruction sheet
CAD
REACh Declaration
RoHs Declaration
Software - Release Notes
circuit breaker Compact NSX400HB2 - Micrologic 6.3 E-M - 320 A - 3 poles 3d
poles description | 3P |
---|---|
protected poles description | 3t |
breaking capacity code | 100 kA |
trip unit name | Micrologic 6.3 E-M |
Magnetic setting range | 320 A |
trip unit protection functions | LSIG |
device application | Distribution |
Write Your Own Review
Main
- Range
- Compact
- Product name
- Compact NSX
- Product or component type
- Circuit breaker
- Device short name
- Compact NSX400HB2
- Device application
- Distribution
- Poles description
- 3P
- Protected poles description
- 3t
- Network type
- AC
- Network frequency
- 50/60 Hz
- [In] rated current
- 320 A ( 65 °C )
400 A ( 40 °C ) - [Ui] rated insulation voltage
- 800 V AC 50/60 Hz
- [Uimp] rated impulse withstand voltage
- 8 kV
- [Ue] rated operational voltage
- 690 V AC 50/60 Hz
- Breaking capacity code
- HB2 (100 kA) AC
- Breaking capacity
- 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ics] rated service breaking capacity
- Ics 100 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 - Suitability for isolation
- Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2 - Utilisation category
- Category A
- Trip unit name
- Micrologic 6.3 E-M
- Trip unit technology
- Electronic
- Trip unit protection functions
- LSIG
- Trip unit rating
- 320 A ( 65 °C )
- Protection type
- Overload protection (long time) L
Instantaneous short-circuit protection I
Short time short-circuit protection S
Ground fault protection G - Pollution degree
- 3 conforming to IEC 60664-1
Complementary
- Control type
- Toggle
- Mounting mode
- Fixed
- Mounting support
- Backplate
- Upside connection
- Front
- Downside connection
- Front
- Auxiliary contact composition
- Without
- Mechanical durability
- 15000 cycles
- Electrical durability
- 12000 cycles 440 V In/2 conforming to IEC 60947-2
3000 cycles 690 V In conforming to IEC 60947-2
6000 cycles 440 V In conforming to IEC 60947-2
6000 cycles 690 V In/2 conforming to IEC 60947-2 - Connection pitch
- 45 mm
- Local signalling
- LED 95 % Ith
LED ready - Motor tripping class
- 10
20
30
5 - Complementary motor protection
- Phase unbalance
Protracted starting time
Stalled rotor
Underload - Long time pick-up adjustment type Ir
- Adjustable 9 settings
- Long time pick-up adjustment range
- 160...320 A
- Long time delay adjustment type
- Adjustable
- [tr] long-time delay adjustment range
- 10 s 7.2 x Ir 10
120 s 1.5 x Ir 5
20 s 7.2 x Ir 20
240 s 1.5 x Ir 10
26 s 6 x Ir 20
30 s 7.2 x Ir 30
38 s 6 x Ir 30
480 s 1.5 x Ir 20
5 s 7.2 x Ir 5
720 s 1.5 x Ir 30
13.5 s 6 x Ir 10
6.5 s 6 x Ir 5 - Thermal memory
- 20 minutes before and after tripping
- Short-time pick-up adjustment type Isd
- Adjustable 9 settings
- [Isd] short-time pick-up adjustment range
- 5...13 x Ir
- Short-time delay adjustment type
- Fixed
- Instantaneous pick-up adjustment type Ii
- Fixed
- Instantaneous pick-up adjustment range
- 4800 A
- Ground-fault pick-up adjustment type
- Adjustable 9 settings
- Ground-fault time delay adjustment type -tg
- Adjustable 5 settings
- [tg] ground-fault time delay adjustment range
- 0...0.4 s
- [Ig] ground-fault pick-up adjustment range
- 64...320 A
- Communication of data
- Demand current and power
Energy metering
Instantaneous and demand values
Maintenance indicators
Maximeters/minimeters
Power quality
Protection and alarm settings
Time-stamped histories and event tables
Phase sequence
Thermal image function - Display type
- LCD display
- Type of measurement
- Energy meter
- Electrical data recording
- Maintenance indicators
- Height
- 255 mm
- Width
- 140 mm
- Depth
- 110 mm
- Product weight
- 6.05 kg
Environment
- Overvoltage category
- Class II
- Electrical shock protection class
- Class II
- Standards
- EN/IEC 60947
- Product certifications
- CCC
Marine
EAC - IP degree of protection
- IP40 conforming to IEC 60529
- IK degree of protection
- IK07 conforming to IEC 62262
- Ambient air temperature for operation
- -35...70 °C
- Ambient air temperature for storage
- -55...85 °C
Offer Sustainability
- Sustainable offer status
- Green Premium product
- RoHS (date code: YYWW)
- Schneider Electric declaration of conformity
- REACh
- Reference not containing SVHC above the threshold
- Product environmental profile
- Available
- Product end of life instructions
- Available
Contractual warranty
- Warranty period
- 18 months 18 months