LUFP1

$1,670.30
Special Order-Generally ships in 14 to 21 Business Days
SKU
LUFP1

Fipio/Modbus communication gateway - 1 Fipio SUB-D9 - 1 RJ45 Modbus

Main
Range
TeSys
Device short name
LUF
Product or component type
Communication gateway
Product compatibility
ATS48

ATV31

ATV312

TeSys U starter-controllers
Complementary
Bus type
Fipio

Modbus
Connector type
Female SUB-D 9 field bus

RJ45 Modbus

RJ45 to a PC
Maximum number of connections
<= 8 Modbus slaves
[Us] rated supply voltage
24 V DC +/- 10 %
Current consumption
100 mA typical

280 mA maximum
Local signalling
LED front panel
Services
Command - bus type: Fipio - functions available: 26 configurable words

Configuration and adjustment - bus type: Fipio - functions available: by gateway mini messaging facility

Monitoring - bus type: Fipio - functions available: 26 configurable words

Profile - bus type: Fipio - functions available: FED C32 or FED C32P
Product weight
0.245 kg
Environment
Electromagnetic compatibility
Electromagnetic emission conforming to IEC 50081-2

Electromagnetic immunity conforming to IEC 61000-6-2
Pollution degree
2 conforming to IEC 60664
Ambient air temperature for installation
5...50 °C
IP degree of protection
IP20
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:LUFP1

   Frequently Asked Questions and Answers


  • How to change the default display to show something other than the output frequency on ATV12 and ATV312 drive?

    Issue: How to change the default display to show something other than the output frequency? Product Line: ATV12, ATV312 Environment: All models and serial numbers. Cause: None Resolution: To adjust the display so that other parameters can be viewed besides RFR, go to MON menu. Select a parameter and press and hold the enter key until the display blinks.
    Read more

  • How to program the ATV31 or ATV312 analog output for 4-20ma, 0-20ma or 0-10 V signal?

    Issue: How to program the ATV31 or ATV312 analog output for 4-20mA, 0-20mA or 0-10 V signal?   Product line:   ATV31, ATV312   Environment:   All range All serial number       Cause: How to get a feedback signal form the ATV312? Resolution:  Steps to program the analog output of the ATV31 or ATV312  1). Press the enter key to REF 2). Turn dial to I-O menu Press enter 3). Turn dial to AO1t Press enter       The following selections are available,...
    Read more

  • What can cause the InF fault in the Altivar 31 and Altivar 312 drives?

    Issue: What can cause the InF fault in the Altivar 31 and ATV312 drives? Product Line: Altivar 31 and ATV312 drives Environment: All  Cause: Internal fault  Resolution: InF indicates an internal fault.   It can occur if there are loose connections inside the drive or if the drive is subjected to electromagnetic interference.  Check the line voltage to the drive. Also, check the voltages on the control terminals, +10 to COM and 24V to COM.  It has been observed that improper wi...
    Read more

  • What is the pin-out of the RJ45 socket of an ATV31 / 312 for connection of Modbus, CanOpen and PowerSuite cables

         The RJ45 socket of the ATV31/312 can be used for connection to the following networks and accessories:      a PLC via a Modbus bus or via a CANopen network      a PC/laptop loaded with PowerSuite software      The VW3A31101 remote display terminal      The Pin out of the RJ45 socket of the ATV31 is as follows:      Pin no.         &nbs...
    Read more

  • How can I configure an output on the ATV31 /312 / 320 for a mechanical brake control?

    A mechanical brake can be controlled by the ATV31 / 312 / 320 drive R1 or R2 relay output. It is preferable to use R2 because R1 is often reserved as the fault contact. It is possible to control a mechanical brake in two different ways on the ATV31 / 312 / 320 drive using a relay output:   Please note that for the ATV320 drives, the menu structure has changed slightly and first you must access the FULL menu as follows: RDY > CONF > FULL Once in the FULL menu, you will see the SI...
    Read more

User guide
  • file image LULC032-LULC033, Modbus Communication Module (EN) (pdf) download image`
  • file image LUFP1 v1, Fipio/Modbus RTU Gateway (pdf) download image`
Catalogue
  • file image Altivar 312 variable speed drives catalogue (pdf) download image`
  • file image Catalog: Soft start/soft stop units Altistart 48 (pdf) download image`
Instruction sheet
  • file image LUFP7-S186, LULC033+LUFP7 Profibus DP kit (pdf) download image`
CAD
  • file image Starter-controllersgatewayFIPIO/Modbus (dwf) download image`
  • file image Starter-controllersgatewayFIPIO/Modbus (dwg) download image`
  • file image Starter-controllersgatewayFIPIO/Modbus (dxf) download image`
  • file image Starter-controllersgatewayFIPIO/Modbus (wmf) download image`
Catalogue Page
  • file image Variable speed drives ATV 312 (pdf) download image`
End of life manual
  • file image TeSys LC1K09-K16 - EoLi (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech