Issue: Where to find the thermal overload reset button on the U-Line starter? Product Line: Contactors and Starters IEC Environment: North American Products Resolution: The reset handle is located on the power base and moves to the tripped position upon sensing a short circuit or overload fault.
Read more
Issue: Can the TeSys U motor starters be used on a single phase system with a grounded neutral? Product Line: TeSys U - GIC Product LUB12, LUB32 Environment: US Product Cause: Product Application Resolution: Yes, these starters can be used in this type of setup. If the power wiring is grounded at the motor as well, an imbalance between hot and neutral can result which can cause nuisance tripping.
Read more
All control unit of Tesys U are designed for AC load applications only. Due to the TeSys U design specifications and accessories limitations, it is not allowed to use Tesys U on DC load.
Read more
Issue: Tesys U function modules Product Line: TeSys™ U Open Motor Starter Environment: North American Products Resolution: It provides indication between an overload trip and a short circuit trip. It also provides for remote or automatic reset after a thermal fault.
Read more
When specifying which auxiliary to add to TeSys U motor starters, we must understand for what purpose. Thermal overload is LUFDH11 Switch status is LUFN11 etc. Please see below options: Please find attached data sheet TeSys_U_LUFDH11.pdf
Read more