LTMR27MFM

$2,330.41
Special Order-Generally ships in 14 to 21 Business Days
SKU
LTMR27MFM

motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus

Main
Range
TeSys
Product name
TeSys T
Device short name
LTMR
Product or component type
Motor controller
Device application
Equipment monitoring and control
Measurement current
1.35...27 A
[Us] rated supply voltage
100...240 V AC 50/60 Hz
Current consumption
8...62.8 mA
Supply voltage limits
93.5...264 V AC
Communication port protocol
Modbus
Bus type
Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, RJ45 with 2 shielded twisted pairs

Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, terminal block with 2 shielded twisted pairs
Complementary
[Ui] rated insulation voltage
690 V conforming to CSA C22.2 No 14

690 V conforming to EN/IEC 60947-1

690 V conforming to UL 508
[Uimp] rated impulse withstand voltage
4 kV for supply, inputs and outputs conforming to EN/IEC 60947-4-1

6 kV for current or voltage measurement circuit conforming to EN/IEC 60947-4-1

0.8 kV for communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand
100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating
0.5 A gG for control circuit

4 A gG for output
Protection type
Earth-leakage protection

Phase failure

Reverse polarity protection

Thermal overload protection

Thermal protection

Overload

Phase unbalance

Locked rotor

Overload (long time)

Load fluctuation

Power factor variation
Network and machine diagnosis type
Phase fault and earth fault trip counters

Remaining operating time before overload tripping

Running hours counter/operating time

Starting current and time

Waiting time after overload tripping

Fault recording

Event recording

Trip context information

Trip history information

Motor control command recording
Logic input number
6
Input current
3.1 mA at 100 V

7.5 mA at 240 V
Current state 0 guaranteed
Logic input : 0...40 V and <= 15 mA for 25 ms
Current state 1 guaranteed
Logic input : 79...264 V and >= 2 mA for 25 ms
Maximum operating frequency
2 Hz
Load current
5 A at 250 V AC for logic output

5 A at 30 V DC for logic output
Permissible power
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)

30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Operating rate
1800 cyc/h
Contacts type and composition
1 NO + 1 NC fault signal

3 NO
Metering type
Earth-fault current

Phase current I1, I2, I3 RMS

Temperature

Average current Iavg

Imbalance current
Measurement accuracy
3 % power factor (cos φ > 0.6)

+/- 30 min/year internal clock

0,02 temperature

5...15 % earth fault current internal measurement (for current > 0.2 A)

1 % current

1 % voltage (100...830 V)

5 % active and reactive power

5 % earth fault current external measurement (< 5 % or 0.01 A)
Overvoltage category
III
Connection pitch
5.08 mm
Connections - terminals
Connector, 1 flexible cable with cable end 0.25...2.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 1 flexible cable without cable end 0.2...2.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 1 flexible cable without cable end 0.25...2.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 1 solid cable without cable end 0.2...2.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 2 flexible cable with cable end 0.2...1 mm² /AWG 24...AWG 14 for control circuit

Connector, 2 flexible cable without cable end 0.2...1.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 2 flexible cable without cable end 0.5...1.5 mm² /AWG 24...AWG 14 for control circuit

Connector, 2 solid cable without cable end 0.2...1 mm² /AWG 24...AWG 14 for control circuit
Tightening torque
0.5...0.6 N.m, 3 mm flat screwdriver for control circuit
Pollution degree
3
Electromagnetic compatibility
● electrostatic discharge 3 (8 kV air, 6 kV contact), conforming to EN/IEC 61000-4-2

● fast transients immunity test other circuits level 3 (2 kV), conforming to EN/IEC 61000-4-4

● fast transients immunity test on supply and relay outputs level 4 (4 kV), conforming to EN/IEC 61000-4-4

● conducted RF disturbances (10 V), conforming to EN/IEC 61000-4-6

● surges serial mode (1 kV) control circuit, conforming to EN/IEC 61000-4-5

● surges common mode (2 kV) communication, conforming to EN/IEC 61000-4-5

● surges common mode (2 kV) control circuit, conforming to EN/IEC 61000-4-5

● radiated RF fields 3 (10 V/m), conforming to EN/IEC 61000-4-3

● voltage dips and interruptions immunity test (70 %, 500 ms), conforming to EN/IEC 61000-4-11

● surges serial mode (0.5 kV) temperature sensor, conforming to EN/IEC 61000-4-5

● surges common mode (1 kV) temperature sensor, conforming to EN/IEC 61000-4-5

● surges serial mode (2 kV) relay outputs and supply, conforming to EN/IEC 61000-4-5

● surges common mode (4 kV) relay outputs and supply, conforming to EN/IEC 61000-4-5
Width
91 mm
Height
61 mm
Depth
122.5 mm
Product weight
0.53 kg
Web services
Web server
Compatibility code
LTMR
Environment
Standards
EN 60947-4-1

IACS E10

IEC 60947-4-1

UL 508

CSA C22.2 No 14
Product certifications
ABS

ATEX

BV

CCC

CSA

C-Tick

DNV

GL

KERI

LROS (Lloyds register of shipping)

NOM

RINA

RMRoS

UL

EAC
Protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30

48 h conforming to EN/IEC 60070-2-11

TH conforming to EN/IEC 60068
Fire resistance
650 °C conforming to EN/IEC 60695-2-12

960 °C conforming to UL 94
Ambient air temperature for operation
-20...60 °C
Ambient air temperature for storage
-40...80 °C
Operating altitude
<= 2000 m without derating
Mechanical robustness
● shocks half sine wave acceleration (15 Gn for 11 ms) conforming to EN/IEC 60068-2-27

● vibrations mounted on symmetrical rail (1 Gn, 5...300 Hz) conforming to EN/IEC 60068-2-6

● vibrations plate mounted (4 Gn, 5...300 Hz) conforming to EN/IEC 60068-2-6
IP degree of protection
IP20
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:LTMR27MFM

   Frequently Asked Questions and Answers


  • TeSys T Operating Modes and IO Logic

    Issue: What are the different TeSys T Operating modes? How are they different?  Product Line: TeSys T Motor Management Controller Environment: North American Products Cause: Installation and Application  Resolution: There are six main types of operating modes. Overload, independent, reverser, two-step, two-speed, and custom operating mode. Each has different wiring as well as specific behaviors for the TeSys T inputs and outputs.  See attached for more information.  Operating M...
    Read more

  • How to use TeSys T Custom Logic with SoMove

    You will find in attach Presentation all basic step to create a custom Logic TeSys T motor management device T includes pre-defined modes and large possibilities to adjust parameters by configuring the product with SoMove. Before deciding to customize with specific Custom Logic, make sure you cannot meet customer needs with pre-defined mode and accurate configuration You can also easily change Input/Output behavior using only the Logic Input and Logic output dedicated area in pre-defined programs If Custo...
    Read more

  • Can TeSys T be used for Single Phase application.

    Yes, TeSys T can be used in Single Phase application.  For a Single Phase application, you pass the First Phase cable through the first internal CT and the Second Phase cable/Neutral cable through the third internal CT.
    Read more

  • Reset Button: combination starter with Tesys T

    Issue: If a combination starter is ordered with a Tesys T overload relay will the door of the enclosure have a reset button? Product Line: Combination Starters Environment: NEMA Combination Starters Cause: Product Characteristics Resolution: Yes it will, unless the combination starter comes in a NEMA 12/3R which specifically excludes a reset button on the door. This can be seen by looking at the combination starter class and type in the Schneider Electric Digest.
    Read more

  • What is the explanation of the Parameter FLC1 in TeSys T.

    FLC1 is the parameter to enter the Motor nominal current in TeSys T. In this parameter, the Motor nominal current is entered as a percentage of the rated value of the TeSys T. Example:  For TeSys T of range 8Amps (LTMR08) and a motor of 2 Amps nominal current, you have to set the FLC1 value to 25% because the Motor nominal current is 25% of the full load current of TeSys T Module (LTMR08). This means that the current in register 466 (value of current in percent) take the value of 100% when ...
    Read more

User guide
  • file image TeSys T DTM for FDT Container & Custom Logic Editor - Online Help (pdf) download image`
  • file image TeSys T - Use in explosive atmospheres (pdf) download image`
Instruction sheet
  • file image LTM R - Motor management controller - Instruction sheet (pdf) download image`
CAD
  • file image ModBus relay (pdf) download image`
  • file image ModBus relay (stp) download image`
  • file image Motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus (pdf) download image`
  • file image Motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus (stp) download image`
  • file image Motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus (dwg) download image`
Certificate
  • file image CB Certificate TeSys T, LTMR/LTMEV, made in China, according to IEC 60947-4-1 Ed3 (pdf) download image`
  • file image CB Certificate TeSys T, LTMR/LTMEV, made in China, according to IEC 60947-4-1 Ed3 (pdf) download image`
End of life manual
  • file image End-of-Life Instructions TeSys T (pdf) download image`
Product environmental
  • file image Motor management system (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech