LR97D25M7

$381.49
Special Order-Generally ships in 14 to 21 Business Days
SKU
LR97D25M7

electronic overload relay for motor TeSys - 5...25 A - 200...240 V AC

Main
Range
TeSys
Product name
TeSys D
Device short name
LR97
Product or component type
Electronic overcurrent relay
Relay application
Locked rotor, mechanical jamming I > 3 x Isetting

Overload Imax > Isetting

Sensitivity to phase failure
Product compatibility
LC1D09...D38
Network type
AC
[Us] rated supply voltage
200...240 V AC
Thermal protection adjustment range
5...25 A
[Ue] rated operational voltage
600 V AC 50/60 Hz for power circuit conforming to CSA

600 V AC 50/60 Hz for power circuit conforming to UL

690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
Quantity per set
Set of 10
Complementary
Network frequency
50...60 Hz
Mounting support
Direct on contactor

Rail
Tripping threshold
5...21 A
Surge withstand
6 kV conforming to IEC 61000-4-5
Contacts type and composition
1 C/O
[Ith] conventional free air thermal current
3 A for control circuit
Protection type
BS fuse 3 A - for control circuit

GB2 circuit breaker 3 A - for control circuit

GG fuse 3 A - for control circuit
Maximum power
28 W at 110 V DC conforming to IEC 60947

28 W at 220 V DC conforming to IEC 60947

55 W at 24 V DC conforming to IEC 60947

55 W at 48 V DC conforming to IEC 60947

140 VA at 48 V AC conforming to IEC 60947

360 VA at 110 V AC conforming to IEC 60947

360 VA at 220 V AC conforming to IEC 60947

70 VA at 24 V AC conforming to IEC 60947
[Ui] rated insulation voltage
600 V power circuit conforming to CSA

600 V power circuit conforming to UL

690 V power circuit conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV
Phase failure sensitivity
< 3 s
Reset
Automatic reset 120 s fixed

Electrical by interruption of power supply for minimum 0.1 s

Manual reset
Time range
0.2...10 s - O-time knob

0.3...10 s - O-time knob

0.5..30 s - D-time knob
Signalling function
2 LEDs
Connections - terminals
Control circuit : cable 1 cable 1...25 mm² - cable stiffness: flexible - with cable end

Control circuit : cable 1 cable 1...25 mm² - cable stiffness: flexible - without cable end

Power circuit : cable 1 cable 1...4 mm² - cable stiffness: flexible - with cable end

Power circuit : cable 1 cable 1.5...10 mm² - cable stiffness: flexible - without cable end

Power circuit : lug-clamp 1 cable 1...4 mm² - cable stiffness: flexible - with cable end

Power circuit : lug-clamp 1 cable 1.5...10 mm² - cable stiffness: flexible - without cable end

Control circuit : cable 2 cable 1...25 mm² - cable stiffness: flexible - with cable end

Control circuit : cable 2 cable 1...25 mm² - cable stiffness: flexible - without cable end

Control circuit : lug-clamp 1 cable 1...25 mm² - cable stiffness: flexible - with cable end

Control circuit : lug-clamp 1 cable 1...25 mm² - cable stiffness: flexible - without cable end

Control circuit : lug-clamp 2 cable 1...25 mm² - cable stiffness: flexible - with cable end

Control circuit : lug-clamp 2 cable 1...25 mm² - cable stiffness: flexible - without cable end
Tightening torque
Control circuit : 0.6...1.2 N.m - on lug-clamp

Power circuit : 2 N.m - on cable
Height
67.5 mm
Width
45 mm
Depth
67.5 mm
Product weight
0.172 kg
Environment
Standards
IEC 60255-6

IEC 60947
Product certifications
CSA

GOST

UL
Protective treatment
TH conforming to IEC 60068
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-25...60 °C conforming to IEC 60947-4-1
Ambient air temperature for storage
-30...80 °C
Operating altitude
2000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Shock resistance
15 gn 11 ms conforming to IEC 60068-2-7
Vibration resistance
4 gn conforming to IEC 60068-2-6
Dielectric strength
2 V at 50 Hz conforming to IEC 60255-5
Resistance to electrostatic discharge
6 kV in indirect mode

8 kV in air
Resistance to radiated fields
10 V/m level 3
Resistance to fast transients
2 kV
Disturbance radiated/conducted
10 V conforming to EN 61000-4-6

Class A conforming to EN 55011
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:LR97D25M7

   Frequently Asked Questions and Answers


  • What is the replacement for the Tesys D Contactor LC1D65U7?

    use the new code - LC1D65AU7 3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC See link for Data Sheet: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7
    Read more

  • How to mount the Rectifier DR5TE on TeSys F range of contactor.

    The DR5TE4U rectifier is mounted separately off the coil on a little support sold with the coil. Refer attachment for the mounting instruction of DR5TE Rectifier. Mounting Instruction DR5TE.pdf
    Read more

  • What is the timer for TeSys contactors

     The timer is LATD2
    Read more

  • what coil voltage is the LC1D25N7 TeSys D?

    it is 415v a.c.
    Read more

  • Is there an lu9bc20 Alternative for TeSys U?

    The LU9BC20 and LUA1C200 have been combined into the same device = LUA1C20.
    Read more

Catalogue
  • file image TeSys catalogue - 2018 - chapter B11 Overload relays TeSys LRK, LRD, LR9, RM1, LT3 (pdf) download image`
Instruction sheet
  • file image LR97 D Relais de surcharge électroniques instantanés (pdf) download image`
  • file image LR97 D Electronic Over Current Relays (pdf) download image`
  • file image LR97 D Relais de surcharge électroniques instantanés (pdf) download image`
  • file image LR97 D Relais de surcharge électroniques instantanés (pdf) download image`
  • file image LR97 D Relais de surcharge électroniques instantanés (pdf) download image`
CAD
  • file image TeSys LR97D Electronic over current relay (pdf) download image`
  • file image TeSys LR97D Electronic over current relay (stp) download image`
Certificate
  • file image CCC TeSys LR97D - TeSys LR97D (pdf) download image`
End of life manual
  • file image End-of-Life Instructions TeSys LR97D (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech