The DR5TE4U rectifier is mounted separately off the coil on a little support sold with the coil. Refer attachment for the mounting instruction of DR5TE Rectifier. Mounting Instruction DR5TE.pdf
Read more
Tesys F (LC1F*) uses linear translation movement of contacts,hence double break pole type operation is obtained.
Read more
The maximum DC voltage for TeSys F range contactors is 125 Volt per pole. This voltage is applicable for the specification of L/R
Read more
Issue: What mechanical interlock can be used to interlock two tesys F contactors with different ratings and frame sizes? Product Family: Tesys F contactors, Tesys contactors, LC1F Resolution: Please see attached page for reference of the below components- Upper Contactor Lower Contactor[1] Mechanical Interlock Kit Catalog # LC1F185/LC1F1854 or LC1F225/LC1F2254 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FG4F LC1F265/LC1F2654 OR LC1F330/LC1F3304 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9F...
Read more
Issue: How do you remove the coil on TeSys LC1F F series contactors? Product Line: TeSys F Line Contactors and Accessories Environment: North American Products Cause: ​Would like to remove the coil from an F line contactor Resolution: Ensure power is off Remove wires to the coil Locate the olue or orange button* at the edge of the metal enclosure on the line side of the contactor Be sure there is sufficient clearance beside the contactor to allow the coil to slide out of its location. The coi...