use the new code - LC1D65AU7 3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC See link for Data Sheet: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7
Read more
Yes,Tesys D (LC1D*) uses linear translation movement,hence double breaking of pole is obtained,please find attached document in support of it. Tesys D double break.JPG
Read more
The maximum DC voltage for TeSys D range contactor is 75 Volt per pole. This voltage is applicable for the specification of L/R
Read more
Issue: Checking on the Tesys D-line relays contact ratings. Product Line: Tesys D Contactors Environment: IEC Contactors and Starters Resolution: The contacts are rated NEMA A600 10 amps continuous, and NEMA Q600 2.5 amps continuous.
Read more
Issue: Will the LA4DC1U diode suppressor mount to current Tesys D DC coils? Product Line: IEC contactors and starters Environment: Products sold and used in the United States Resolution: No. The LA4DC1U diode unit will only fit the older TeSys D contactors. Tesys D DC coils include suppression automatically, it`s not needed.