K63E003WP

cam changeover switch - 3-pole - 60° - 63 A - screw mounting
SKU
K63E003WP
$432.43
Documents and Downloads
Certificate
  • K10, K30, K50, K63, K115, K150 Cam switches (html)
  • K1 K2 K10 K30 K50 K63 K115 K150 Cam switches (pdf)
Declaration of conformity
  • K30, K50, K63, K115, K150 Cam switches (pdf)
Description
cam changeover switch - 3-pole - 60° - 63 A - screw mounting
More Information
More Information
poles description3P
IP degree of protectionIP40
fixing mode4 holes
Operator ActionBlack
IP-ClassIP40
[Ith] conventional free air thermal current63 A
component nameK63
cam switch functionReversing switch
product mountingFront mounting
rotary handle padlockingWithout
returnWithout
off positionWith Off position
switching positionsLeft: 0° - 300°, Right: 0° - 60°
cam switch head typeWith front plate
type of operatorHandle
degree of proctectionIP40
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Harmony K
Product or component type
Complete cam switch
Component name
K63
[Ith] conventional free air thermal current
63 A
Product mounting
Front mounting
Fixing mode
4 holes
Cam switch head type
With front plate 64 x 64 mm
Type of operator
Black handle
Rotary handle padlocking
Without
Presentation of legend
With metallic legend, 1 - 0 - 2 black marking
Cam switch function
Reversing switch
Return
Without
Off position
With Off position
Poles description
3P
Switching positions
Left: 0° - 300°

Right: 0° - 60°
IP degree of protection
IP40 conforming to IEC 529

IP40 conforming to NF C 20-010
Complementary
Switching angle
60 °
[Ui] rated insulation voltage
690 V degree of pollution 3 conforming to EN 60947-1

690 V degree of pollution 3 conforming to IEC 60947-1
Short-circuit current
10000 A
Short-circuit protection
80 A by cartridge fuse, type gG
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 947-1

6 kV conforming to IEC 947-1
Contact operation
Slow-break
Positive opening
With
Electrical connection
Captive screw clamp terminals flexible, 2 x 10 mm²

Captive screw clamp terminals solid, 2 x 16 mm²
Tightening torque
2.5 N.m
Switching capacity in mA
20000 mA DC at 140 V 3 contact(s) for inductive load (T = 50 ms)

20000 mA DC at 48 V 1 contact(s) for inductive load (T = 50 ms)

20000 mA DC at 95 V 2 contact(s) for inductive load (T = 50 ms)

30000 mA DC at 120 V 2 contact(s) for resistive load (T = 1 ms)

30000 mA DC at 180 V 3 contact(s) for resistive load (T = 1 ms)

30000 mA DC at 60 V 1 contact(s) for resistive load (T = 1 ms)

55000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms)

55000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms)

55000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms)

63000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms)

63000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms)

63000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms)

63000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms)

63000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms)

63000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms)

63000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms)

63000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms)

63000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms)
Mechanical durability
300000 cycles
CAD overall width
64 mm
CAD overall height
64 mm
CAD overall depth
132 mm
Product weight
0.54 kg
Environment
Standards
EN/IEC 60947-3
Product certifications
CULus 120 V 3 hp 1 phase

CULus 240 V 10 hp 3 phases

CULus 480 V 25 hp 3 phases

CULus 240 V 7.5 hp 1 phase
Protective treatment
TC
Ambient air temperature for operation
-25...55 °C
Ambient air temperature for storage
-40...70 °C
Electrical shock protection class
Class II conforming to NF C 20-030

Class II conforming to IEC 60536
Contractual warranty
Warranty period
18 months