K63E003WP
cam changeover switch - 3-pole - 60° - 63 A - screw mounting
SKU
K63E003WP
$432.43
Certificate
Declaration of conformity
cam changeover switch - 3-pole - 60° - 63 A - screw mounting
poles description | 3P |
---|---|
IP degree of protection | IP40 |
fixing mode | 4 holes |
Operator Action | Black |
IP-Class | IP40 |
[Ith] conventional free air thermal current | 63 A |
component name | K63 |
cam switch function | Reversing switch |
product mounting | Front mounting |
rotary handle padlocking | Without |
return | Without |
off position | With Off position |
switching positions | Left: 0° - 300°, Right: 0° - 60° |
cam switch head type | With front plate |
type of operator | Handle |
degree of proctection | IP40 |
Write Your Own Review
Main
- Range of product
- Harmony K
- Product or component type
- Complete cam switch
- Component name
- K63
- [Ith] conventional free air thermal current
- 63 A
- Product mounting
- Front mounting
- Fixing mode
- 4 holes
- Cam switch head type
- With front plate 64 x 64 mm
- Type of operator
- Black handle
- Rotary handle padlocking
- Without
- Presentation of legend
- With metallic legend, 1 - 0 - 2 black marking
- Cam switch function
- Reversing switch
- Return
- Without
- Off position
- With Off position
- Poles description
- 3P
- Switching positions
- Left: 0° - 300°
Right: 0° - 60° - IP degree of protection
- IP40 conforming to IEC 529
IP40 conforming to NF C 20-010
Complementary
- Switching angle
- 60 °
- [Ui] rated insulation voltage
- 690 V degree of pollution 3 conforming to EN 60947-1
690 V degree of pollution 3 conforming to IEC 60947-1 - Short-circuit current
- 10000 A
- Short-circuit protection
- 80 A by cartridge fuse, type gG
- [Uimp] rated impulse withstand voltage
- 6 kV conforming to EN 947-1
6 kV conforming to IEC 947-1 - Contact operation
- Slow-break
- Positive opening
- With
- Electrical connection
- Captive screw clamp terminals flexible, 2 x 10 mm²
Captive screw clamp terminals solid, 2 x 16 mm² - Tightening torque
- 2.5 N.m
- Switching capacity in mA
- 20000 mA DC at 140 V 3 contact(s) for inductive load (T = 50 ms)
20000 mA DC at 48 V 1 contact(s) for inductive load (T = 50 ms)
20000 mA DC at 95 V 2 contact(s) for inductive load (T = 50 ms)
30000 mA DC at 120 V 2 contact(s) for resistive load (T = 1 ms)
30000 mA DC at 180 V 3 contact(s) for resistive load (T = 1 ms)
30000 mA DC at 60 V 1 contact(s) for resistive load (T = 1 ms)
55000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms)
55000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms)
55000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms)
63000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms)
63000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms)
63000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms)
63000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms)
63000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms)
63000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms)
63000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms)
63000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms)
63000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms) - Mechanical durability
- 300000 cycles
- CAD overall width
- 64 mm
- CAD overall height
- 64 mm
- CAD overall depth
- 132 mm
- Product weight
- 0.54 kg
Environment
- Standards
- EN/IEC 60947-3
- Product certifications
- CULus 120 V 3 hp 1 phase
CULus 240 V 10 hp 3 phases
CULus 480 V 25 hp 3 phases
CULus 240 V 7.5 hp 1 phase - Protective treatment
- TC
- Ambient air temperature for operation
- -25...55 °C
- Ambient air temperature for storage
- -40...70 °C
- Electrical shock protection class
- Class II conforming to NF C 20-030
Class II conforming to IEC 60536
Contractual warranty
- Warranty period
- 18 months