Rack references | a in mm | a in in. |
---|---|---|
BMXXBP0400 and BMXXBP0400H | 242.4 | 09.54 |
BMXXBP0600 and BMXXBP0600H | 307.6 | 12.11 |
BMXXBP0800 and BMXXBP0800H | 372.8 | 14.68 |
BMXXBP1200 and BMXXBP1200H | 503.2 | 19.81 |
The following table indicates the calculated MTBF for M340 CPU's. The values are in hours and years for continuous usage at 30 degrees C / 86 degrees F. Reference number Continuous hours @ 30 degrees C Continuous years @ 30 degrees C BMXP341000 413347 47 BMXP342010 389418 44 BMXP342020 391864 45 BMXP342030 384868 44 Legacy KB System (APS) Data: RESL186926 V1.0, Originally authored by DaSo on 07/11/2007, Last Edited by DaSo on 07/11/2007 Related range...
Read more
Goals and Symptoms How to interpret the front panel lights when diagnosing problems with the M340. Causes and Fixes Modicon M340 Processor Troubleshooting The Modicon M340 Programmable Automation Controller is a Mid-range automation system providing small size, yet powerful 32-bit processor for demanding OEM machine and industrial process applications. It is programmed using our cross-platform IEC 61131-3 application development software, Unity Pro (v3.0 or higher). The front panel has a series o...
Read more
Goals and Symptoms Provide a part number list for the Modicon M340 PLC platform Causes and Fixes Please refer to the attached Automation PRODUCTS part list for the Modicon M340 PLC platform. Legacy KB System (APS) Data: RESL186758 V2.0, Originally authored by DaSo on 07/09/2007, Last Edited by DaSo on 07/16/2007 Related ranges: Modicon M340
Read more
The Modicon M340 PLC can only be programmed using the Unity Pro software. Legacy KB System (APS) Data: RESL210819 V1.0, Originally authored by DaSo on 03/01/2013, Last Edited by DaSo on 03/01/2013 Related ranges: Modicon M340
Read more
No, the Modicon M340 does not support HART signals. However, there is a Telefast block which can be used to filter out the digital component of the HART signal allowing only the analog component to be seen by the analog input. The part number of the block is ABE7CPA31E. The M580 does have a HART solution using the BMX Analog IO. The BMEAHI0812 HART Analog Input and BMEAHO0412 Hart Analog Output. R-122018 Legacy KB System (APS) Data: RESL210758 V1.0, Originally authored by DaSo on 02/25/20...
Read more
Rack references | a in mm | a in in. |
---|---|---|
BMXXBP0400 and BMXXBP0400H | 242.4 | 09.54 |
BMXXBP0600 and BMXXBP0600H | 307.6 | 12.11 |
BMXXBP0800 and BMXXBP0800H | 372.8 | 14.68 |
BMXXBP1200 and BMXXBP1200H | 503.2 | 19.81 |