BMXDRA0805H

discrete output module M340 - 8 O relay - 12..24 V DC - severe environment
SKU
BMXDRA0805H
$972.19
Documents and Downloads
User guide
  • Modicon M580 Standalone System Planning Guide for Frequently Used Architectures (pdf)
  • Modicon M580, Hardware Reference Manual (pdf)
  • Modicon M580 - RIO Modules, Installation and Configuration Guide (pdf)
  • Modicon M580 Change Configuration on the Fly User Guide (pdf)
Catalogue
  • Catalogue Modicon X80 Automation platform - English version 2018/07 (web pdf format) (pdf)
Certificate
  • CSA_225844_1815060-70013205_M340_M580_X80_NOV2017 (PDF)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • RUSSIAN_METROLOGICAL_CERTIFICATE_65910_M340_M580_X80_MAY2017 (pdf)
  • HazLoc_cCSAus_225844_70013205_M340_M580_X80_NOV2017 (pdf)
Declaration of conformity
  • DCE_M340_M580_X80_SEP2018 (pdf)
  • ACMA_RCM_M340_M580_X80_MAR2016 (pdf)
End of life manual
  • Modicon M340 Modules, Product End-of-Life Instructions (pdf)
Marine certificate
  • KRS_Marine Certificate_Modicon_M340_X80_PLC (pdf)
  • MERCHANT_NAVY_PLC_INSTALLATION (pdf)
  • RMRS_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • RINA_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • DNV-GL_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • CCS_Marine Certificate_M580_M340_X80_PLCs (pdf)
  • BV_Marine Certificate_M340-M580-X80_PLCs (pdf)
Product environmental
  • Modicon M340 Modules, Product Environmental Profile (pdf)
REACh Declaration
  • discrete output module M340 - 8 O relay - 12..24 V DC - severe environment (pdf)
RoHs Declaration
  • discrete output module M340 - 8 O relay - 12..24 V DC - severe environment (pdf)
Description
discrete output module M340 - 8 O relay - 12..24 V DC - severe environment
More Information
More Information
product or component typeDiscrete output module
discrete output number8
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Modicon X80
Product or component type
Discrete output module
Product specific application
For severe environments
Discrete output number
8 conforming to EN/IEC 61131-2
Discrete output type
Relay
Discrete output voltage
12...24 V 10...34 V DC

24...240 V 10...264 V AC
Complementary
[Ith] conventional free air thermal current
3 A
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
<= 2.7 W
Response time on output
<= 10 ms activation

<= 8 ms deactivation
Typical current consumption
100 mA at 3.3 V DC
MTBF reliability
1573341 H
Protection type
Overvoltage protection, inductive AC network

Overvoltage protection, inductive DC network

External overload protection

External short-circuit protection
Output overload protection
Use 1 fast blow fuse per channel or group of channel
Output overvoltage protection
Use discharge diode on each output DC

Use RC circuit on each output AC

Use ZNO surge limiter on each output AC
Output short-circuit protection
Use 1 fast blow fuse per channel or group of channel
Minimum switching current
1 mA 5 V DC
Electrical durability
1000000 cycles AC-12 30 VA 48 V at 70 °C

1000000 cycles DC-12 14.4 VA 24 V at 70 °C

1000000 cycles DC-13 14.4 VA 24 V at 70 °C

2000000 cycles AC-15 14.4 VA 48 V 0.35 at 70 °C

2000000 cycles DC-13 6 VA 24 V at 70 °C

300000 cycles DC-12 24 VA 24 V at 70 °C

500000 cycles AC-12 66 VA 48 V at 70 °C

500000 cycles AC-15 14.4 VA 24 V 0.35 at 70 °C

5000000 cycles AC-15 6 VA 48 V 0.35 at 70 °C

700000 cycles AC-12 30 VA 24 V at 70 °C

100000 cycles AC-15 132 VA 200...240 V at 70 °C

100000 cycles AC-15 220 VA 200...240 V 0.35 at -25...60 °C

1000000 cycles AC-12 110 VA 110...120 V at -25...60 °C

1000000 cycles AC-12 132 VA 200...240 V at 70 °C

1000000 cycles AC-12 220 VA 200...240 V at -25...60 °C

1000000 cycles AC-12 50 VA 48 V at -25...60 °C

1000000 cycles AC-12 66 VA 110...120 V at 70 °C

1000000 cycles AC-15 110 VA 200...240 V 0.35 at -25...60 °C

1000000 cycles AC-15 60 VA 200...240 V at 70 °C

1000000 cycles DC-12 24 W 24 V at -25...60 °C

1000000 cycles DC-13 24 W 24 V at -25...60 °C

10000000 cycles AC-15 10 VA 110...120 V 0.35 at -25...60 °C

10000000 cycles AC-15 10 VA 200...240 V 0.35 at -25...60 °C

10000000 cycles AC-15 6 VA 110...120 V 0.35 at 70 °C

10000000 cycles AC-15 6 VA 200...240 V at 70 °C

150000 cycles AC-15 110 VA 110...120 V 0.35 at -25...60 °C

150000 cycles AC-15 60 VA 110...120 V 0.35 at 70 °C

1500000 cycles AC-15 30 VA 110...120 V 0.35 at 70 °C

1500000 cycles AC-15 50 VA 110...120 V 0.35 at -25...60 °C

2000000 cycles AC-15 24 VA 48 V 0.35 at -25...60 °C

2000000 cycles DC-13 10 W 24 V at -25...60 °C

300000 cycles DC-12 40 W 24 V at -25...60 °C

3000000 cycles AC-15 30 VA 200...240 V at 70 °C

3000000 cycles AC-15 50 VA 200...240 V 0.35 at -25...60 °C

500000 cycles AC-12 110 VA 48 V at -25...60 °C

500000 cycles AC-12 132 VA 110...120 V at 70 °C

500000 cycles AC-12 220 VA 110...120 V at -25...60 °C

500000 cycles AC-15 10 VA 48 V 0.35 at -25...60 °C

500000 cycles AC-15 24 VA 24 V 0.35 at -25...60 °C

700000 cycles AC-12 50 VA 24 V at -25...60 °C
Status LED
1 LED green for module operating (RUN)

1 LED per channel green for channel diagnostic

1 LED red for module I/O

1 LED red for module error (ERR)
Product weight
0.145 kg
Environment
IP degree of protection
IP20
Product certifications
ATEX

CE

CSA

UL

RCM

IEC-Ex

Merchant Navy

EAC
Standards
EN/IEC 61131-2

EN/IEC 61010-2-201

UL 61010-2-201

CSA C22.2 No 61010-2-201
Dielectric strength
2000 V AC at 50/60 Hz 1 min
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient air temperature for storage
-40...85 °C
Ambient air temperature for operation
-25...70 °C
Relative humidity
5...95 % without condensation 55 °C
Protective treatment
Conformal coating Humiseal 1A33

TC
Environmental characteristic
Corrosion resistance

Dust resistant
Operating altitude
0...2000 m

2000...5000 m (with derating factor)
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information
Contractual warranty
Warranty period
18 months