BMXDDM16022H

discrete I/O module M340 - 8 I - 24 V DC - 8 O - solid state- severe environment
SKU
BMXDDM16022H
$1,230.57
Documents and Downloads
User guide
  • Modicon M580 Standalone System Planning Guide for Frequently Used Architectures (pdf)
  • Modicon M580, Hardware Reference Manual (pdf)
  • Modicon M580 - RIO Modules, Installation and Configuration Guide (pdf)
  • Modicon M580 Change Configuration on the Fly User Guide (pdf)
Catalogue
  • Catalogue Modicon X80 Automation platform - English version 2018/07 (web pdf format) (pdf)
Certificate
  • CSA_225844_1815060-70013205_M340_M580_X80_NOV2017 (PDF)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • ATEX_14ATEX3025X_M340_M580_X80_JUL2017 IECEX_INE14.0070X_M340_M580_X80_JUL2017 ATEX_INSTRUCTIONS_DCE_M340_M580_X80_JUL2017 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • DCC_EAC_M340_M580_X80_PS_SEP2016 DCC_EAC_M340_M580_X80_SEP2016 (pdf)
  • RUSSIAN_METROLOGICAL_CERTIFICATE_65910_M340_M580_X80_MAY2017 (pdf)
  • HazLoc_cCSAus_225844_70013205_M340_M580_X80_NOV2017 (pdf)
Declaration of conformity
  • DCE_M340_M580_X80_SEP2018 (pdf)
  • ACMA_RCM_M340_M580_X80_MAR2016 (pdf)
End of life manual
  • Modicon M340 Modules, Product End-of-Life Instructions (pdf)
Marine certificate
  • KRS_Marine Certificate_Modicon_M340_X80_PLC (pdf)
  • MERCHANT_NAVY_PLC_INSTALLATION (pdf)
  • RMRS_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • RINA_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • DNV-GL_Marine Certificate_Modicon_M340_M580_X80_PLCs (pdf)
  • CCS_Marine Certificate_M580_M340_X80_PLCs (pdf)
  • BV_Marine Certificate_M340-M580-X80_PLCs (pdf)
Product environmental
  • Modicon M340 Modules, Product Environmental Profile (pdf)
REACh Declaration
  • discrete I/O module M340 - 8 I - 24 V DC - 8 O - solid state- severe environment (pdf)
RoHs Declaration
  • discrete I/O module M340 - 8 I - 24 V DC - 8 O - solid state- severe environment (pdf)
Description
discrete I/O module M340 - 8 I - 24 V DC - 8 O - solid state- severe environment
More Information
More Information
product or component typeDiscrete I/O module
discrete input number8
discrete output number8
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Modicon X80
Product or component type
Discrete I/O module
Product specific application
For severe environments
Discrete input number
8
Input type
Current sink (logic positive)
Discrete input voltage
24 V DC positive
Discrete input current
3.5 mA
Input compatibility
With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
Discrete output number
8
Discrete output type
Solid state
Discrete output voltage
24 V 19...30 V DC at 60 °C

24 V 26.4 V DC at 70 °C
Discrete output current
0.5 A
Complementary
Sensor power supply
26.4 V at 70 °C

19...30 V
Voltage state 1 guaranteed
>= 11 V
Current state 1 guaranteed
>= 3 mA
Voltage state 0 guaranteed
<= 5 V
Current state 0 guaranteed
<= 1.5 mA
Current per channel
0.625 A at 60 °C

0.55 A at 70 °C
Current per module
<= 4.4 A at <= 70 °C

<= 5 A at <= 60 °C
Leakage current
<= 0.5 mA at state 0
[Ures] residual voltage
1.2 V at state 1
Input impedance
6800 Ohm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
<= 3.7 W
DC typical filtering time
4 ms
DC maximum filtering time
7 ms
Response time on output
1.2 ms
Paralleling of outputs
Yes : 2 maximum
Typical current consumption
100 mA at 3.3 V DC

30 mA at 24 V DC
Current consumption
<= 111 mA at 3.3 V DC

<= 67 mA at 24 V DC
MTBF reliability
447581 H
Protection type
Overvoltage protection on output

Reverse polarity protection on input

Reverse polarity protection on output

1 external fuse per group of input channel 0.5 A fast blow
Output overload protection
With electronic circuit breaker 1.5 In < Id < 2 In

With current limiter
Output overvoltage protection
With transil diode
Output short-circuit protection
With 2 A external fuse
Reverse polarity protection
Reverse mounted diode
Voltage detection threshold
< 14 V DC preactuator fault

< 14 V DC sensor fault

> 18 V DC preactuator OK

> 18 V DC sensor OK
Tungsten load
<= 6 W
Switching frequency
0.5/LI² Hz
Overload time
<= 15 ms
Load impedance ohmic
<= 48 Ohm
Status LED
1 LED green for module operating (RUN)

1 LED per channel green for channel diagnostic

1 LED red for module I/O

1 LED red for module error (ERR)
Product weight
0.115 kg
Environment
IP degree of protection
IP20
Product certifications
ATEX

CE

CSA

UL

RCM

IEC-Ex

Merchant Navy

EAC
Standards
EN/IEC 61131-2

EN/IEC 61010-2-201

UL 61010-2-201

CSA C22.2 No 61010-2-201
Dielectric strength
1500 V AC at 50/60 Hz 1 minute, output/ground

1500 V AC at 50/60 Hz 1 minute, output/internal logic

1500 V AC at 50/60 Hz 1 minute, primary/secondary

500 V DC 1 minute, between group of inputs and outputs
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient air temperature for storage
-40...85 °C
Ambient air temperature for operation
-25...70 °C
Relative humidity
5...95 % without condensation 55 °C
Protective treatment
Conformal coating Humiseal 1A33

TC
Environmental characteristic
Corrosion resistance

Dust resistant
Operating altitude
0...2000 m

2000...5000 m (with derating factor)
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information
Contractual warranty
Warranty period
18 months