Right, Front and Rear View
Issue: Does SoMachine V4.2 include the ATV process (ATV6xx and ATV9xx) DTMs? Product Line: SoMachine V4.2 Resolution: The ATV process DTMs are not yet validated and integrated within SoMachine V4.2. You will have to manually import an EDS file for these drives in order to control them through SoMachine. They will be in SoMachine V4.3
Read more
Issue: Does SoMachine have a library to control the ATV process drives? Product Line: SoMachine Resolution: SoMachine V4.3 includes DTM libraries for the Altivar Process Drives (ATV600 and ATV900 series).
Read more
Issue: What is Thermal Sensor Error (t1CF) on the Altivar Process 900? Product Line: Variable Frequency Drives Environment: Applies to Altivar Process 900 ATV930 ATV940 ATV960 Cause: Drive displaying \'t1CF\' when wiring the sensor to \'AI1\' and \'COM\' Resolution: t1CF: AI1 thermal sensor Error Probable Cause: The thermal sensor monitoring function has detected a thermal sensor error on analog input AI1: Open circuit, or Short circuit Remedy: Verify the sensor and its wiring, replace the sensor...
Read more
Issue: Is the VW3A1101 compatible with the ATV600 and ATV900 series process drives? Product Line: ATV600 and ATV900 series Environment: All models, All serial numbers Cause: Information not available in current literature. Resolution: The VW3A1101 keypad is not compatible with the Altivar Process series drives. It is only compatible with ATV61, ATV71, ATV212, ATV312, and ATV32 series drives.
Read more
Issue: What communications are available for the ATV900 series Process drives? Product line: Altivar Process Drive (900, 930, 950. 960, 980) Environment: All serial numbers for Altivar Process Drive Cause: n/a Resolution: The ATV900 series drives comes standard with 4x RJ45 communication ports. 2 port is Ethernet IP/Modbus TCP, 2 ports are Modbus serial. Integrated Communication Protocols​ EtherNet/IP and Modbus TCP Dual port EtherNet/IP adapter including standard CIP objects (AC/DC dr...
Read more
Right, Front and Rear View
X1 | X2 | X3 |
---|---|---|
≥ 100 mm (3.94 in.) | ≥ 100 mm (3.94 in.) | ≥ 10 mm (0.39 in.) |
Mount the device in a vertical position (±10°). This is required for cooling the device.
Do not mount the device close to heat sources.
Leave sufficient free space so that the air required for cooling purposes can circulate from the bottom to the top of the drive.
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
It is possible to connect either 1 or 3 sensors on terminals AI1 or AI3
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
Set the switch to Ext if using PLC outputs with NPN transistors.