ATS48C66Q

soft starter for asynchronous motor - ATS48 - 605 A - 230..415 V - 160..500 KW
SKU
ATS48C66Q
$19,144.13
Documents and Downloads
Software - Released
  • SoMove V2.6.5 (FDT Standalone) (exe)
  • SoMove V2.6.5 (FDT Standalone) (pdf)
User guide
  • ATS48 User manual (pdf)
  • ATS48 Modbus manual (pdf)
  • 1) ATS48 Getting started (pdf)
  • ATS48 Getting Started Annex for UL508 (SCCR) (pdf)
Catalogue
  • Catalog: Soft start/soft stop units Altistart 48 (pdf)
CAD
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dwf)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dwg)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dxf)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (wmf)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dwf)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dwg)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (dxf)
  • references ATS48C41Q, ATS48C48Q, ATS48C59Q, ATS48C66Q, ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y (wmf)
Certificate
  • ATS48_CSA_CERTIFICATE (pdf)
  • E184727 UL GENERIC CERTIFICATES (pdf)
  • ATV12 C-TICK CERTIFICATE (pdf)
  • ATS48 C-TICK CERTIFICATE (pdf)
  • ATS48 EU DECLARATION (pdf)
Marine certificate
  • DNV-GL Marine Certificate Altistart ATS48 motor starters (PDF)
Product environmental
  • Altistart 48 410 to 1200 Amps - Standard applications, Product Environmental Profile (pdf)
Description
soft starter for asynchronous motor - ATS48 - 605 A - 230..415 V - 160..500 KW
More Information
More Information
motor power kW160 kW, 315 kW, 355 kW, 400 kW, 500 kW
Icl nominal current660 A, 1143 A
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Altistart 48
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Heavy duty industry and pumps
Device short name
ATS48
[Us] rated supply voltage
230...415 V (- 15...10 %)
Motor power kW
160 kW at 230 V (connection in the motor supply line) for severe applications

315 kW at 230 V (connection to the motor delta terminals) for standard applications

315 kW at 400 V (connection in the motor supply line) for severe applications

355 kW at 400 V (connection in the motor supply line) for standard applications

400 kW at 400 V (connection to the motor delta terminals) for severe applications

500 kW at 400 V (connection to the motor delta terminals) for standard applications
Power dissipation in W
For standard applications 1731 W

For severe applications 1958 W
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 5 In)
IcL starter rating
660 A (connection in the motor supply line) for severe applications

660 A (connection in the motor supply line) for standard applications

1143 A (connection to the motor delta terminals) for standard applications

1143 A (connection to the motor delta terminals) for severe applications
IP degree of protection
IP00
Complementary
Assembly style
With heat sink
Function available
External bypass (optional)
Supply voltage limits
195...456 V
Supply frequency
50...60 Hz (- 5...5 %)
Network frequency
47.5...63 Hz
Device connection
In the motor supply line

To the motor delta terminals
Factory setting current
605 A
[Uc] control circuit voltage
220 - 15 % to 415 + 10 %, 50/60 Hz
Control circuit consumption
80 W
Discrete output number
2
Discrete output type
(LO1) logic output 0 V common configurable

(LO2) logic output 0 V common configurable

(R1) relay outputs fault relay NO

(R2) relay outputs end of starting relay NO

(R3) relay outputs motor powered NO
Output absolute accuracy precision
+/- 5 %
Minimum switching current
Relay outputs 10 mA at 6 V DC
Maximum switching current
Logic output 0.2 A at 30 V DC

Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms

Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms
Discrete input number
5
Discrete input type
PTC, 750 Ohm at 25 °C

(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input voltage
24 V (<= 30 V)
Discrete input logic
Positive logic (Stop, Run, LI3, LI4) state 0 < 5 V and <= 2 mA, state 1 > 11 V and >= 5 mA
Supply inrush current
Adjustable 0.4...1.3 Icl
Analogue output type
(AO) current output 0-20 mA or 4-20 mA <= 500 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure (line)

Thermal protection (motor)

Thermal protection (starter)
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
670 mm
Width
400 mm
Depth
300 mm
Product weight
51.4 kg
Power range
110...220 kW at 200...240 V 3 phases

250...500 kW at 380...440 V 3 phases

250...500 kW at 200...240 V 3 phases
Motor starter type
Soft starter
Environment
Electromagnetic compatibility
Conducted and radiated emissions conforming to IEC 60947-4-2 level A

Damped oscillating waves conforming to IEC 61000-4-12 level 3

Electrostatic discharge conforming to IEC 61000-4-2 level 3

Immunity to electrical transients conforming to IEC 61000-4-4 level 4

Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3 level 3

Voltage/current impulse conforming to IEC 61000-4-5 level 3
Standards
EN/IEC 60947-4-2
Product certifications
CCC

CSA

C-Tick

DNV

GOST

NOM 117

SEPRO

TCF

UL
Vibration resistance
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6

1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level
55 dB
Pollution degree
Level 3 conforming to IEC 60664-1
Relative humidity
0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
40...60 °C with current derating of 2 % per °C

-10...40 °C without derating
Ambient air temperature for storage
-25...70 °C
Operating altitude
<= 1000 m without derating

> 1000...2000 m with current derating of 2.2 % per additional 100 m
Contractual warranty
Warranty period
18 months