ATS22C41Q

soft starter-ATS22-control 220V-power 230V(110kW)/400...440V(220kW)
SKU
ATS22C41Q
$7,657.46
Documents and Downloads
Software - Released
  • SoMove V2.6.5 (FDT Standalone) (exe)
  • SoMove V2.6.5 (FDT Standalone) (pdf)
User guide
  • 1) ATS22 - Quick Start guide (pdf)
  • ATS22 User manual (pdf)
Catalogue
  • Catalog: Soft start/soft stop units Altistart 22 (pdf)
Certificate
  • ATS22 CSA CERTIFICATE (pdf)
  • ATS22 UL CERTIFICATE (pdf)
  • ATS22 EU DECLARATION (pdf)
REACh Declaration
  • soft starter-ATS22-control 220V-power 230V(110kW)/400...440V(220kW) (pdf)
RoHs Declaration
  • soft starter-ATS22-control 220V-power 230V(110kW)/400...440V(220kW) (pdf)
Description
soft starter-ATS22-control 220V-power 230V(110kW)/400...440V(220kW)
More Information
More Information
icl starter rating410 A
motor power kW110 kW, 220 kW
Icl nominal current410 A
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Altistart 22
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Pumps and fans
Component name
ATS22
Network number of phases
3 phases
[Us] rated supply voltage
230...440 V - 15...10 %
Motor power kW
110 kW 230 V

220 kW 400 V

220 kW 440 V
Factory setting current
388 A
Power dissipation in W
177 W for standard applications
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 3.5 In)
IcL starter rating
410 A connection in the motor supply line for standard applications
IP degree of protection
IP00
Complementary
Assembly style
With heat sink
Function available
Internal bypass
Supply voltage limits
195...484 V
Supply frequency
50...60 Hz - 10...10 %
Network frequency
45...66 Hz
Device connection
In the motor supply line

To the motor delta terminals
[Uc] control circuit voltage
230 V -15...10 % 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O

Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current
100 mA 12 V DC relay outputs
Maximum switching current
5 A 250 V AC resistive 1 relay outputs

5 A 30 V DC resistive 1 relay outputs

2 A 250 V AC inductive 0.4 20 ms relay outputs

2 A 30 V DC inductive 7 ms relay outputs
Discrete input number
3
Discrete input type
Logic LI1, LI2, LI3 5 mA 4.3 kOhm
Discrete input voltage
24 V <= 30 V
Discrete input logic
Positive logic LI1, LI2, LI3 < 5 V and <= 2 mA > 11 V >= 5 mA
Output current
0.4...1 Icl adjustable
PTC probe input
750 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure line

Thermal protection starter

Thermal protection motor
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
425 mm
Width
206 mm
Depth
299 mm
Product weight
33 kg
Power range
110...220 kW at 380...440 V 3 phases

110...220 kW at 200...240 V 3 phases
Motor starter type
Soft starter
Environment
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2

Damped oscillating waves level 3 IEC 61000-4-12

Electrostatic discharge level 3 IEC 61000-4-2

Immunity to electrical transients level 4 IEC 61000-4-4

Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3

Voltage/current impulse level 3 IEC 61000-4-5
Standards
EN/IEC 60947-4-2
Product certifications
CCC

CSA

C-Tick

GOST

UL
Vibration resistance
1.5 mm 2...13 Hz EN/IEC 60068-2-6

1 gn 13...200 Hz EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Noise level
56 dB
Pollution degree
Level 2 IEC 60664-1
Relative humidity
0...95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation
-10...40 °C without derating

> 40...< 60 °C with current derating 2.2 % per °C
Ambient air temperature for storage
-25...70 °C
Operating altitude
<= 1000 m without derating

> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Available
Contractual warranty
Warranty period
18 months