A9E16066

$190.39
Generally ships in 1 to 2 days
SKU
A9E16066

iRTB relay-delays de-energizing a load upon closing-1C/O - Uc 24-240 VAC/24VDC

Main
Relay application
Time delay relay
Time delay type
Delays de-energizing of a load upon contact closing
Range
Acti 9
Product name
IRT
Device short name
IRTB
Signal contacts composition
1 C/O
Complementary
[Ie] rated operational current
8 A AC 250 V

8 A DC 250 V

0.01 A DC 5 V
Impulse duration
> 100 ms
Local signalling
LED flashing time delay
Type of setting
Time delay configuration by rotary knob
Time delay range
0.1...360000 s
Accuracy error
+/- 10 %
Repeat accuracy
+/- 0.5 %
[Uc] control circuit voltage
24 V DC

24...240 V AC 50/60 Hz
[Us] rated supply voltage
24 V DC

24...240 V AC 50/60 Hz
Mounting mode
Fixed
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
2
Height
93 mm
Width
18 mm
Depth
72 mm
Product weight
0.065 kg
Colour
White
Mechanical durability
>= 5000000 cycles
Electrical durability
AC-1 : >= 100000 cycles
Undervoltage behaviour
100 ms
Connections - terminals
Tunnel type terminals 2 cable(s) 1.5 mm² flexible with cable end

Tunnel type terminals 2 cable(s) 1.5 mm² flexible without cable end

Tunnel type terminals 2 cable(s) 2.5 mm² rigid with cable end

Tunnel type terminals 2 cable(s) 2.5 mm² rigid without cable end
Environment
IP degree of protection
IP20
Immunity to microbreaks
<= 20 ms
Ambient air temperature for operation
-5...55 °C
Ambient air temperature for storage
-40...70 °C
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Available
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:A9E16066

   Frequently Asked Questions and Answers


  • What is the power consumption of timer a9e16066?

    [Ie] rated operational current: 8 A AC 250 V 8 A DC 250 V 0.01 A DC 5 V
    Read more

  • What is the replacement for 16066 Timer?

    The replacement for 16066 Timer is A9E16066. A9E16066 iRTB relay-delays de-energizing a load upon closing-1C/O - Uc 24-240 VAC/24VDC For more information see: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9E16066
    Read more

  • What is the replacement for the 16066?

    The replacement part number for the 16066 is A9E16066 See data sheet for more information....https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=a9e16066
    Read more

  • What is the new version of the Merlin Gerin 16066?

    A9E16066 Time Delay Relay - 8A
    Read more

  • What is the code for a din mount time switch analogue IRTB?

    A9E16066
    Read more

Instruction sheet
  • file image Time delay relays iRTB iRTC (pdf) download image`
CAD
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (dwf) download image`
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (dwg) download image`
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (dxf) download image`
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (wmf) download image`
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (pdf) download image`
  • file image Relay with time delayed iRTA/iRTB/iRTC/iRTH 2P (stp) download image`
  • file image IRT 2P UC 24-240 VCA/24VCC RELAY TIME (zip) download image`
  • file image IRT 2P UC 24-240 VCA/24VCC RELAY TIME (stp) download image`
REACh Declaration
  • file image iRTB relay-delays de-energizing a load upon closing-1C/O - Uc 24-240 VAC/24VDC (pdf) download image`
RoHs Declaration
  • file image iRTB relay-delays de-energizing a load upon closing-1C/O - Uc 24-240 VAC/24VDC (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech