31337

switch-disconnector Compact INS1600 - 1600 A - 4 poles
SKU
31337
$5,691.22
Documents and Downloads
Catalogue
  • COMPACT NSX, COMPACT INS INV and MASTERPACT NW - DC- DC PV catalogue (pdf)
Instruction sheet
  • Compact - Switch disconector INS 630b... 1600, INV 630b... 1600 (pdf)
CAD
  • Auxiliary contactEarly-make contact CAF (dwf)
  • Auxiliary contactEarly-make contact CAF (dwg)
  • Auxiliary contactEarly-make contact CAF (dxf)
  • Auxiliary contactEarly-make contact CAF (wmf)
  • Compact INS630b to INS1600 & INV630b to INV1600 4P; Switch Disconnector (pdf)
  • Compact INS630b to INS1600 & INV630b to INV1600 4P; Switch Disconnector (stp)
End of life manual
  • INS 630B/INS 1600 - INV 630/INV 1600 - EoLi (pdf)
Description
switch-disconnector Compact INS1600 - 1600 A - 4 poles
More Information
More Information
poles description4P
[Ie] rated operational current1250 A, 1450 A, 1600 A
handle colourBlack
visible breakNo
Reviews
Write Your Own Review
Characterstics
Main
Range
Compact
Product name
Compact INS
Product or component type
Switch disconnector
Poles description
4P
Network type
AC

DC
Network frequency
50/60 Hz
[Ie] rated operational current
AC-23A : 1250 A AC 50/60 Hz 220/240 V

AC-23A : 1250 A AC 50/60 Hz 380/415 V

AC-23A : 1250 A AC 50/60 Hz 440/480 V

AC-23A : 1250 A AC 50/60 Hz 500/525 V

AC-23A : 1250 A AC 50/60 Hz 660/690 V

AC-21A : 1250 A AC 50/60 Hz 440/480 V

AC-21B : 1600 A AC 50/60 Hz 380/415 V

AC-22B : 1600 A AC 50/60 Hz 220/240 V

AC-21A : 1450 A AC 50/60 Hz 380/415 V

DC-21A : 1600 A DC 250 V 4 poles in series

AC-22B : 1600 A AC 50/60 Hz 440/480 V

AC-22A : 1250 A AC 50/60 Hz 480 V NEMA

DC-23A : 1600 A DC 125 V 2 poles in series

AC-21B : 1600 A AC 50/60 Hz 500/525 V

AC-21A : 1250 A AC 50/60 Hz 660/690 V

AC-22B : 1600 A AC 50/60 Hz 660/690 V

AC-22A : 1450 A AC 50/60 Hz 220/240 V

AC-22B : 1600 A AC 50/60 Hz 380/415 V

AC-22A : 1250 A AC 50/60 Hz 440/480 V

AC-21B : 1600 A AC 50/60 Hz 220/240 V

DC-22A : 1600 A DC 125 V 2 poles in series

DC-21A : 1600 A DC 125 V 2 poles in series

AC-21B : 1600 A AC 50/60 Hz 440/480 V

AC-23A : 1250 A AC 50/60 Hz 480 V NEMA

AC-21A : 1250 A AC 50/60 Hz 480 V NEMA

AC-22B : 1600 A AC 50/60 Hz 480 V NEMA

AC-22A : 1250 A AC 50/60 Hz 500/525 V

AC-22A : 1250 A AC 50/60 Hz 660/690 V

DC-22A : 1600 A DC 250 V 4 poles in series

AC-21B : 1600 A AC 50/60 Hz 480 V NEMA

AC-21A : 1250 A AC 50/60 Hz 500/525 V

AC-22B : 1600 A AC 50/60 Hz 500/525 V

AC-21A : 1450 A AC 50/60 Hz 220/240 V

AC-21B : 1600 A AC 50/60 Hz 660/690 V

AC-22A : 1450 A AC 50/60 Hz 380/415 V

DC-23A : 1600 A DC 250 V 4 poles in series
[Ui] rated insulation voltage
1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
12 kV
[Ith] conventional free air thermal current
1600 A ( 60 °C )
[Icm] rated short-circuit making capacity
75 kA 690 V AC 50/60 Hz switch-disconnector alone

75 kA 690 V AC 50/60 Hz with upstream protection circuit breaker
[Ue] rated operational voltage
250 V DC

690 V AC 50/60 Hz
Suitability for isolation
Yes
Contact position indicator
Yes
Visible break
No
Pollution degree
3
Complementary
Control type
Direct front rotary handle
Handle colour
Black
Mounting mode
Fixed
Mounting support
Plate

Rail
Upside connection
Front
Downside connection
Front
Maximum power
AC-23 : 400 kW 220/240 V AC 50/60 Hz

AC-23 : 900 kW 500/525 V AC 50/60 Hz

AC-23 : 710 kW 380/400 V AC 50/60 Hz

AC-23 : 800 kW 415 V AC 50/60 Hz
Rated duty
Uninterrupted
Intermittent duty class
Class 120 - 60 %
[Icw] rated short-time withstand current
10 kA ( 20 s ) conforming to IEC 60947-3

20 kA ( 3 s ) conforming to IEC 60947-3

35 kA ( 1 s ) conforming to IEC 60947-3

42 kA ( 0.8 s ) conforming to IEC 60947-3

50 kA ( 0.5 s ) conforming to IEC 60947-3

8 kA ( 30 s ) conforming to IEC 60947-3
Mechanical durability
3000 cycles
Electrical durability
DC-21A : 500 cycles 250 V DC 4 poles in series

AC-21A : 500 cycles 220/240 V AC 50/60 Hz

AC-21A : 500 cycles 380/415 V AC 50/60 Hz

AC-21A : 500 cycles 440/480 V AC 50/60 Hz

AC-21A : 500 cycles 480 V AC 50/60 Hz conforming to NEMA

AC-21A : 500 cycles 500/525 V AC 50/60 Hz

AC-21A : 500 cycles 660/690 V AC 50/60 Hz

AC-21B : 100 cycles 220/240 V AC 50/60 Hz

AC-21B : 100 cycles 380/415 V AC 50/60 Hz

AC-21B : 100 cycles 440/480 V AC 50/60 Hz

AC-21B : 100 cycles 480 V AC 50/60 Hz conforming to NEMA

AC-21B : 100 cycles 500/525 V AC 50/60 Hz

AC-21B : 100 cycles 660/690 V AC 50/60 Hz

AC-22A : 500 cycles 220/240 V AC 50/60 Hz

AC-22A : 500 cycles 380/415 V AC 50/60 Hz

AC-22A : 500 cycles 440/480 V AC 50/60 Hz

AC-22A : 500 cycles 480 V AC 50/60 Hz conforming to NEMA

AC-22A : 500 cycles 500/525 V AC 50/60 Hz

AC-22A : 500 cycles 660/690 V AC 50/60 Hz

AC-22B : 100 cycles 220/240 V AC 50/60 Hz

AC-22B : 100 cycles 380/415 V AC 50/60 Hz

AC-22B : 100 cycles 440/480 V AC 50/60 Hz

AC-22B : 100 cycles 480 V AC 50/60 Hz conforming to NEMA

AC-22B : 100 cycles 500/525 V AC 50/60 Hz

AC-22B : 100 cycles 660/690 V AC 50/60 Hz

AC-23B : 500 cycles 220/240 V AC 50/60 Hz

AC-23B : 500 cycles 380/415 V AC 50/60 Hz

AC-23B : 500 cycles 440/480 V AC 50/60 Hz

AC-23B : 500 cycles 480 V AC 50/60 Hz conforming to NEMA

AC-23B : 500 cycles 500/525 V AC 50/60 Hz

AC-23B : 500 cycles 660/690 V AC 50/60 Hz

DC-21A : 500 cycles 125 V DC 2 poles in series

DC-22A : 500 cycles 125 V DC 2 poles in series

DC-22A : 500 cycles 250 V DC 4 poles in series

DC-23B : 500 cycles 125 V DC 2 poles in series

DC-23B : 500 cycles 250 V DC 4 poles in series
Connection pitch
70 mm
Height
300 mm
Width
410 mm
Depth
146.5 mm
Product weight
18 kg
Environment
Standards
IEC 60947-1

IEC 60947-3
Product certifications
KEMA-KEUR
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Ambient air temperature for operation
-25...70 °C
Ambient air temperature for storage
-50...85 °C
Contractual warranty
Warranty period
18 months