29472

interface and automatic controller - ACP + UA - 220..240 V
SKU
29472
$3,668.21
Documents and Downloads
User guide
  • UA controller - Compact NS100-630/NS630b-1600/Masterpact NT/NW (pdf)
  • Compact NSX100-630 - User guide (pdf)
Catalogue
  • catalog source changeover system- Compact NS/NSX/INS-INV/Masterpact (pdf)
  • TRANSFERPACT SOURCE -CHANGOVER CATALOGUE (pdf)
CAD
  • interface and automatic controller - ACP + UA - 220..240 V (pdf)
  • interface and automatic controller - ACP + UA - 220..240 V (stp)
Description
interface and automatic controller - ACP + UA - 220..240 V
More Information
More Information
product or component typeInterface and control unit
auxiliary supply220...240 V
range of productNSX100...250, NSX400...630, Masterpact NT, Masterpact NW, Compact NS100...630, Compact NS630b...1600
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Compact NS100...630

Compact NS630b...1600

Masterpact NT

Masterpact NW

NSX100...250

NSX400...630
Product or component type
Interface and control unit
Accessory / separate part category
Interlocking accessory
Range compatibility
Compact - Compact NS circuit breaker

Compact - Compact NSX circuit breaker

Masterpact - Masterpact NT circuit breaker

Masterpact - Masterpact NW circuit breaker
Device short name
ACP + UA
[Us] rated supply voltage
220...240 V AC 50/60 Hz
Complementary
Operating mode
Automatic operation

Forced operation on normal source

Forced operation on replacement source

Stop (both normal and replacement source off)
Interlocked device
Compact NS100...630

Compact NS630b...1600

Masterpact NT

Masterpact NW

NSX100...250

NSX400...630
Selection modes
Circuit breaker on N

Circuit breaker on R
Test function
By pressing the test button on the front of the controller
Complementary function
Forced normal source if replacement source not operational during peak-tariff

Selection of type of normal source (single-phase or three-phase)

Setting of maximum startup time for the replacement source

Voluntary transfer to replacement source (e.g. energy management commands)

Additional contact: transfer to replacement source only if contact is closed
Local signalling
Fault trip

Off

On
Input type
Contacts customer voluntary order to transfer to source R
Output type
Contacts customer : indication of operation in automatic or stop mode
[Ith] conventional free air thermal current
8 A
[Ie] rated operational current
DC-12 : 2 A DC 48 V

AC-12 : 4 A AC 440 V

AC-12 : 5 A AC 380/415 V

AC-12 : 8 A AC 110 V

AC-12 : 8 A AC 220/240 V

AC-12 : 8 A AC 24 V

AC-12 : 8 A AC 48 V

AC-13 : 6 A AC 110 V

AC-13 : 6 A AC 220/240 V

AC-13 : 7 A AC 24 V

AC-13 : 7 A AC 48 V

AC-14 : 4 A AC 110 V

AC-14 : 4 A AC 220/240 V

AC-14 : 5 A AC 24 V

AC-14 : 5 A AC 48 V

AC-15 : 3 A AC 220/240 V

AC-15 : 4 A AC 110 V

AC-15 : 5 A AC 24 V

AC-15 : 5 A AC 48 V

DC-12 : 0.4 A DC 250 V

DC-12 : 0.6 A DC 110 V

DC-12 : 8 A DC 24 V

DC-13 : 2 A 24 V
Product compatibility
Compact NS630b...1600

Compact NSX100...250

Compact NSX400...630
Environment
Standards
IEC 947-5-1
IP degree of protection
Connectors : IP20 conforming to EN 60529

Front : IP40 conforming to EN 60529

Side : IP30 conforming to EN 60529
IK degree of protection
Front : IK07 conforming to EN 50102
Contractual warranty
Warranty period
18 months