The 140ACO02000, 140AVO02000, and the 140AMM09000 have one D/A per channel.
Read more
No. Unfortunately, we no longer do a programming cable for this older range of PLC, but a simple wiring diagram attached. Doc1.pdf
Read more
In Modicon Quantum range, I/O scanning works with following Modbus function codes: FC3 for Reading Multiple 4X registers. FC16 for Writing Multiple 4X registers. If both the read and write are filled out then FC23 for Read/Write Multiple 4X registers is used.
Read more
Release Notice Schneider Electric® has become aware of the release of a metasploit module allowing a user to send a stop command to or modify the PLC program of a Modicon Quantum PLC Goals and Symptoms The ability to send commands from Unity Pro software or over UMAS to the controller was already identified in ICS-ALERT-12-020-03 and a response is available in Schneider Electric Resolution 207378. This resolution expands on that. Causes and Fixes Follow the recommendations found in the atta...
Read more
No. This constitutes a configuration change. Mismatched configurations are not allowed in a Modicon Quantum Hot Standby system.
Read more
Jumpers are required between IN (+) and SENSE terminals for all current input ranges.
Pins 1 ... 20 are outputs.
Pins 21 ... 40 are inputs.
For Inputs, the maximum channel to channel working voltage cannot exceed 30Â Vdc.