TMC2TI2

cartridge M221 - 2 temperature inputs - I/O extension
SKU
TMC2TI2
$210.58
Documents and Downloads
User guide
  • Modicon M221 Logic Controller, Hardware Guide (pdf)
  • Modicon TMC2 Cartridges, Hardware Guide (pdf)
  • Modicon TMC2 Cartridges, Programming Guide (pdf)
  • SoMachine Basic - Operating guide (pdf)
Catalogue
  • Modicon M221 logic controllers (pdf)
Instruction sheet
  • Modicon TMC2 - Cartridges, Instruction Sheet (pdf)
CAD
  • Compact Hardwired Logic Controller M221 - Wiring Diagram (zip)
Certificate
  • TM221_TM3_CSA_Certificate (PDF)
Declaration of conformity
  • Modicon DoC TM4_TMC_TM3-Expert (pdf)
End of life manual
  • TMC... Cartridge M241, Product End-of-Life Instructions (pdf)
Marine certificate
  • LR Type Approval TM221 and TM3 (pdf)
  • ABS PDA TM221 and TM3 (pdf)
  • DNV-GL Marine Certificate TM221 PLC (pdf)
Product environmental
  • TMC... Cartridge M241, Product Environmental Profile (pdf)
REACh Declaration
  • cartridge M221 - 2 temperature inputs - I/O extension (pdf)
RoHs Declaration
  • cartridge M221 - 2 temperature inputs - I/O extension (pdf)
Description
cartridge M221 - 2 temperature inputs - I/O extension
More Information
More Information
product or component typeAnalogue input cartridge
input typeTemperature probe, Thermocouple
analogue input typeTemperature probe, Thermocouple
analogue input number2
Reviews
Write Your Own Review
Characterstics
Main
Range of product
Modicon M221
Product or component type
Analogue input cartridge
Product compatibility
Modicon M221C
Analogue input number
2
Complementary
Analogue input type
Thermocouple, input range: - 200...1000 °C for thermocouple J

Thermocouple, input range: - 200...1300 °C for thermocouple K

Thermocouple, input range: 0...1760 °C for thermocouple R

Thermocouple, input range: 0...1760 °C for thermocouple S

Thermocouple, input range: 0...1820 °C for thermocouple B

Thermocouple, input range: - 200...400 °C for thermocouple T

Thermocouple, input range: - 200...1300 °C for thermocouple N

Thermocouple, input range: - 200...800 °C for thermocouple E

Thermocouple, input range: 0...2315 °C for thermocouple C

Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000)

Temperature probe, input range: - 200...850 °C (Pt 100)

Temperature probe, input range: - 200...600 °C (Pt 1000)
Analogue input resolution
14 bits
LSB value
0.1 °C
Sampling duration
125 ms (thermocouple)

250 ms (temperature probe)
Absolute accuracy error
+/- 0.1 % of full scale Pt 100/Pt 1000, Ni 100/ Ni 1000 25 °C

+/- 0.4 % of full scale thermocouple K - 200...0 °C 25 °C

+/- 0.1 % of full scale thermocouple K 0...1300 °C 25 °C

+/- 0.4 % of full scale thermocouple J - 200...0 °C 25 °C

+/- 0.1 % of full scale thermocouple J 0...1000 °C 25 °C

+/- 0.4 % of full scale thermocouple E - 200...0 °C 25 °C

+/- 0.1 % of full scale thermocouple E 0...800 °C 25 °C

+/- 0.4 % of full scale thermocouple T - 200...0 °C 25 °C

+/- 0.1 % of full scale thermocouple T 0...400 °C 25 °C

+/- 0.4 % of full scale thermocouple N - 200...0 °C 25 °C

+/- 0.1 % of full scale thermocouple N 0...1300 °C 25 °C

+/- 6 °C thermocouple R, S 0...200 °C 25 °C

+/- 0.1 % of full scale thermocouple R, S 200...1760 °C 25 °C

+/- 0.1 % of full scale thermocouple C 0...2315 °C 25 °C
Temperature drift
+/- 0.02 %FS/°C
Repeat accuracy
+/- 0.5 %FS
Non-linearity
+/- 0.01 %FS
Cross talk
<= 1 LSB
Type of cable
Twisted shielded pairs cable
Electrical connection
2 screw terminal blocks (pitch 3.81 mm) 1.5 mm² 3 for inputs
Cable distance between devices
Twisted shielded pairs cable: 30 m for input
Insulation
Non-insulated between analogue input and internal logic
Height
41 mm
Depth
15 mm
Width
35 mm
Product weight
0.015 kg
Input impedance
>= 1 MOhm
Environment
Immunity to microbreaks
10 ms
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information