module TM3 - 8 inputs spring

Main
Range of product
Modicon TM3
Product or component type
Discrete input module
Range compatibility
Modicon M221

Modicon M241

Modicon M251
Discrete input number
8 input conforming to IEC 61131-2 Type 1
Discrete input logic
Sink or source (positive/negative)
Discrete input voltage
24 V
Discrete input current
7 mA for input
Complementary
Discrete I/O number
8
Current consumption
5 mA at 5 V DC via bus connector at state off

0 mA at 24 V DC via bus connector at state on

0 mA at 24 V DC via bus connector at state off

24 mA at 5 V DC via bus connector at state on
Discrete input voltage type
DC
Voltage state 1 guaranteed
15...28.8 V for input
Current state 1 guaranteed
>= 2.5 mA for input
Voltage state 0 guaranteed
0...5 V for input
Current state 0 guaranteed
<= 1 mA for input
Input impedance
3.4 kOhm
Response time
4 ms for turn-on

4 ms for turn-off
Local signalling
1 LED per channel green for input status
Electrical connection
Removable spring terminal block pitch 5.08 mm with 11 terminal(s) of 2.5 mm² connection capacity for inputs
Insulation
Non-insulated between inputs

500 V AC between input and internal logic
Marking
CE
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715

Top hat type TH35-7.5 rail conforming to IEC 60715

Plate or panel with fixing kit
Height
90 mm
Depth
84.6 mm
Width
27.4 mm
Product weight
0.085 kg
Environment
Standards
EN/IEC 61131-2

EN/IEC 61010-2-201
Product certifications
C-Tick

cULus
Resistance to electrostatic discharge
4 kV (on contact) conforming to EN/IEC 61000-4-2

8 kV (in air) conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3

3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3

1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients
1 kV for I/O conforming to EN/IEC 61000-4-4
Surge withstand
1 kV for I/O (DC) in common mode conforming to EN/IEC 61000-4-5
Resistance to conducted disturbances
10 Vrms at 0.15...80 MHz conforming to EN/IEC 61000-4-6

3 Vrms at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Radiated emissions, test level: 40 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 30...230 MHz) conforming to EN/IEC 55011

Radiated emissions, test level: 47 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 230...1000 MHz) conforming to EN/IEC 55011
Ambient air temperature for operation
-10...55 °C for horizontal installation

-10...35 °C for vertical installation
Ambient air temperature for storage
-25...70 °C
Relative humidity
10...95 % without condensation in operation

10...95 % without condensation in storage
IP degree of protection
IP20 with protective cover in place
Pollution degree
2
Operating altitude
0...2000 m
Storage altitude
0...3000 m
Vibration resistance
3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail

3 gn (vibration frequency: 8.4...150 Hz) on DIN rail

3.5 mm (vibration frequency: 5...8.4 Hz) on panel

3 gn (vibration frequency: 8.4...150 Hz) on panel
Shock resistance
15 gn (test wave duration:11 ms)
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information
Write Your Own Review
You're reviewing:TM3DI8G

   Frequently Asked Questions and Answers


  • Can I disable a TM3 module in SoMachine?

    Issue: Set the TM3 module as optional in SoMachine Product Line: Modicon TM3 Resolution: It's possible to set a TM3 module as optional in SoMachine. This will allow you to run your program without faulting the TM3 bus even if the TM3 module is not physically present on the rack.  See attached screenashot for how to do that in SoMachine.  TM3.png
    Read more

  • What is the maximum number of expansion modules for M221 controllers

    Local I/O Maximum configuration: 7 Modicon TM3 expansion modules associated with an M221 logic controller. Depending on the expansion module references, there may be fewer than 7. Remote I/O Maximum configuration: 14 Modicon TM3 expansion modules (7 local modules + 7 remote modules) with the Modicon TM3 bus expansion system (transmitter module and receiver module is not included in the maximum number of modules). TM3 expansion modules are powered by logic controllers via the bus connector on the side ...
    Read more

  • Reverse PID mode in Modicon M241/M251

    There is no input to select between direct/inverse direction at the PID function block from the Util library. The FB_PID function block (Toolbox library) is from Schneider and has additional features. With FB_PID function block from the Toolbox library in SoMachine to change the regulation direction user can use negative P-factor (i_rKp) The basic PID function must remain the same.
    Read more

  • Can we use 800 IOs with Modicon m580 Safety System without impact TUV certification

    There is no issue to use 800 series IOs without any impact on TÜV certificate on a M580 Safety configuration. As a general rule, all of Remote Distributed equipments on Ethernet allowed in M580 system could be considered as “non-interfering” for Safety M580 modules. However, of course, 800 series IOs data are not supposed to be used to perform safety functions.
    Read more

  • Video: Setting Persistent Variables with the Modicon M221 in SoMachine Basic

    The video demonstrates how to set up persistent variables and save them in the memory words of SoMachine Basic.  
    Read more

User guide
  • file image Modicon M241 Logic Controller - High Speed Counting, HSC Library Guide (pdf) download image`
  • file image Modicon M241 Logic Controller - System Functions and Variables PLCSystem, Library Guide (pdf) download image`
  • file image Modicon M221 Logic Controller, Hardware Guide (pdf) download image`
  • file image Modicon M241 Logic Controller, Hardware Guide (pdf) download image`
  • file image Modicon M241 Logic Controller - PTOPWM, Library Guide (pdf) download image`
  • file image Modicon M241 Logic Controller, Programming Guide (pdf) download image`
  • file image Modicon M251 Logic Controller, Hardware Guide (pdf) download image`
  • file image Modicon TM3 - Digital I/O Modules, Hardware Guide (pdf) download image`
  • file image Modicon TM3 (SoMachine Basic) - Expansion Modules Configuration, Programming Guide (pdf) download image`
  • file image SoMachine Basic - Operating guide (pdf) download image`
Catalogue
  • file image Modicon TM3 I/O expansion modules for Modicon controllers (pdf) download image`
Instruction sheet
  • file image TM3 Digital I/O Modules, Instruction sheet (pdf) download image`
CAD
  • file image Compact Hardwired Logic Controller M221 - Wiring Diagram (zip) download image`
  • file image Compact Hardwired Logic Controller M241 - Wiring Diagram (zip) download image`
  • file image Distributed Modbus TCP Logic Controller M251 - Wiring Diagram (zip) download image`
  • file image Compact EtherNet/IP Logic Controller M251 - Wiring Diagram (zip) download image`
Certificate
  • file image TM221_TM3_CSA_Certificate (PDF) download image`
Declaration of conformity
  • file image Modicon DoC TM3 Accessory (pdf) download image`
  • file image RCM_SupplierDeclarationOfConformity_TM221_TM3 (pdf) download image`
End of life manual
  • file image Modicon TM3 Expansion Module, Product End-of-Life Instructions (pdf) download image`
Marine certificate
  • file image LR Type Approval TM221 and TM3 (pdf) download image`
  • file image ABS PDA TM221 and TM3 (pdf) download image`
  • file image DNV-GL Marine Certificate TM221 PLC (pdf) download image`
Product environmental
  • file image Modicon TM3 Expansion Module, Product Environmental Profile (pdf) download image`
REACh Declaration
  • file image module TM3 - 8 inputs spring (pdf) download image`
RoHs Declaration
  • file image module TM3 - 8 inputs spring (pdf) download image`

Dimensions Drawings

Dimensions



(*)
8.5 mm/0.33 in. when the clamp is pulled out.


Mounting and Clearance

Spacing Requirements





Mounting on a Rail



Incorrect Mounting





Mounting on a Panel Surface



(1)
Install a mounting strip
Mounting Hole Layout





Connections and Schema

Digital Input Module (8-channel, 24 Vdc)
Wiring Diagram



The 3 COM terminals are connected internally.
(A)
Sink wiring (positive logic)
(B)
Souce wiring (negative logic)