LV438603
circuit breaker Compact NSX100M - TMD - 20 A - 2 poles 2d
SKU
LV438603
$276.88
User guide
Catalogue
Instruction sheet
CAD
circuit breaker Compact NSX100M - TMD - 20 A - 2 poles 2d
poles description | 2P |
---|---|
protected poles description | 2t |
Current Rating | 100 A |
breaking capacity code | 25 kA |
Interrupt Rating | 25 kA, 8 kA, 18 kA, 85 kA |
trip unit name | TM-D |
Magnetic setting range | 20 A |
trip unit protection functions | LI |
device application | Distribution |
Write Your Own Review
Main
- Range
- Compact
- Product name
- Compact NSX
- Product or component type
- Circuit breaker
- Device short name
- Compact NSX100M
- Device application
- Distribution
- Poles description
- 2P
- Protected poles description
- 2t
- Network type
- DC
- Network frequency
- 50/60 Hz
- [In] rated current
- 100 A ( 40 °C )
100 A ( 65 °C ) - [Ui] rated insulation voltage
- 750 V AC 50/60 Hz IEC 60947-2
- [Uimp] rated impulse withstand voltage
- 8 kV conforming to IEC 60947-2
- [Ue] rated operational voltage
- 500 V DC conforming to IEC 60947-2
690 V AC 50/60 Hz conforming to IEC 60947-2 - Breaking capacity code
- M (25 kA) AC
- Breaking capacity
- 85 kA Icu at 250 V DC 1P conforming to IEC 60947-2
85 kA Icu at 48/125 V DC 1P conforming to IEC 60947-2
18 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 500 V DC 2P conforming to IEC 60947-2 - [Ics] rated service breaking capacity
- Ics 18 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 18 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 25 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 8 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 85 kA 220 V AC 50/60 Hz conforming to IEC 60947-2 - Suitability for isolation
- Yes conforming to IEC 60947-2
- Utilisation category
- Category A
- Trip unit name
- TM-D
- Trip unit technology
- Thermal-magnetic
- Trip unit protection functions
- LI
- Trip unit rating
- 20 A ( 40 °C )
- Protection type
- Overload protection (thermal) L
Short-circuit protection (magnetic) I - Pollution degree
- 3 conforming to IEC 60947
Complementary
- Connection pitch
- 35 mm
- Local signalling
- Positive contact indication
- Magnetic tripping current
- 190 A
- Long time pick-up adjustment type Ir
- Fixed
- Long time pick-up adjustment range
- 0.8...1 x In
- Instantaneous pick-up adjustment type Ii
- Fixed
- Instantaneous pick-up adjustment range
- 190 A
- Height
- 161 mm
- Width
- 70 mm
- Depth
- 86 mm
- Control type
- Toggle
- Mounting mode
- Fixed
- Mounting support
- Backplate
- Upside connection
- Front
- Downside connection
- Front
- Auxiliary contact composition
- Without
- Mechanical durability
- 20000 cycles
- Electrical durability
- 10000 cycles 277 V AC 50/60 Hz In conforming to IEC 60947-2
20000 cycles 277 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Environment
- Standards
- EN/IEC 60947
- Product certifications
- CCC
Marine
EAC - IP degree of protection
- IP40 conforming to IEC 60529
- IK degree of protection
- IK07 conforming to EN 50102
Offer Sustainability
- Sustainable offer status
- Green Premium product
- RoHS (date code: YYWW)
- Schneider Electric declaration of conformity
- REACh
- Reference not containing SVHC above the threshold
- Product environmental profile
- Available
- Product end of life instructions
- Available
Contractual warranty
- Warranty period
- 18 months 18 months