Attached is the dimensions for the Magelis GTO series of HMI's GTO dimensions.zip
Read more
Issue The XBTGT4330 and XBTGT4340 are legacy HMI and no longer in production. What are the options for replacing them? Product Line Legacy Magelis HMI, XBTGT series Environment Physical Magelis HMI Resolution The XBTGT4330 is a 7.5\' (320x240 pixels) panel without Video playback capability. The XBTGT4340 is a 7.5\' (320x240 pixels) panel with Video playback capability. There is no official direct replacement from the XBTGT4340 product page, however, these are the closest options: Opt...
Read more
The replacement for the Magelis XBTGT6330 is HMIGTO6310. No change for cut?out dimensions. Connection to the Profibus DP, DeviceNet and CanOpen field buses is not possible, Only RS232 serial link is possible with COM1. Use COM2 with RJ45 connector for RS485 serial. There is no alarm output or loudspeaker output SD cards should be used instead of CF cards. (capacity up to 4Gb).
Read more
Issue: Does the Magelis XBTGT7340 offer single mode fiber? Product Line: Magelis XBTGK/GT, HMIGK/GTO/GTU/STO/STU Environment: Cause: Resolution: The Magelis XBTGT range does not have single mode fiber as an option. These targets only comes with a copper connection for Ethernet. Our suggestion would be to use a media converter type switch that has a single mode fiber. We offer a low end switch, part number TCSESU103F2CS0, which has 8 copper ports and 2 single mode fiber ports.
Read more
The XBTGT1335 is replaced by either the HMIGTO1310 or the HMISTU655. I have attached data sheets for all three units for review and comparison. Magelis_GTO_HMIGTO1310.pdfMagelis_STO___STU_HMISTU655.pdfXBTGT1335.pdf
Read more
A | B | C | R | ||||
---|---|---|---|---|---|---|---|
mm | in. | mm | in. | mm | in. | mm | in. |
301.5 (+1, -0) | 11.87 (+0.04, -0) | 227.5 (+1, -0) | 8.96 (+0.04, -0) | 1.6...5 | 0.06...0.2 | 3Â max. | 0.12 max. |
When installing the panel in a slanted position with an incline more than 30°, the ambient temperature must not exceed 40 °C (104 °F). You may need to use forced air cooling (fan,A/C) to ensure the ambient operating temperature is 40°C or less (104 °F or less).