Wrong 140cpu53414b file delivered with CD OS V2.5 for UnityPro V3.1

370 views  December 25, 2018

Goals and Symptoms

If you want to upgrade a Quantum Plc from Concept to Unity, you have to use a intermediate OS before loading the UnityPro OS. For the 140CPU534B is delivered a wrong intermediate OS.

Facts and Changes

UnityPro V3.1, CD OS V2.5

Causes and Fixes

A usable intermediate OS is available on PL@NET: Modicon Quantum / Software/Firmware / 140CPU53414B firmware upgrade for Unity users, Version V2.32, 15 Jun 2007. The intermediate OS for V2.32 \'concept_to_unity_53414b.bin\' can also be used for the OS V2.5.

Attachments

Links to PL@NET and telemecanique:
(Removed File URL: https://planet.schneider-electric.com/C1256F0F00560EB2/all/C125713F005265E2C12572F300354289?OpenDocument&L=EN&)https://planet.schneider-electric.com/C1256F0F00560EB2/all/C125713F005265E2C12572F300354289?OpenDocument&L=EN&,
(Removed File URL: https://download.telemecanique.com/85256D570066CD16/all/C125713F005265E2C12572F300354289?OpenDocument&L=EN)https://download.telemecanique.com/85256D570066CD16/all/C125713F005265E2C12572F300354289?OpenDocument&L=EN


Legacy KB System (APS) Data: RESL191467 V1.0, Originally authored by KlSP on 03/18/2008, Last Edited by KlSP on 03/18/2008