Issue Setup of the IP Address for the BMXNOR0200H Product Line Modicon x80 Enviroment Unity Pro Resolution In Unity Pro, first configure the BMXNOR0200H module in the PLC rack. 1. Open the PLC Bus view. 2. Right-click on an empty slot and select New Device. 3. In the Part Number column, expand Communication folder to see the available modules, including the BMXNOR0200H. Next create a new network by selecting the Network Folder under the Communication folder. Right click the Network folder and select t...
Read more
Title What premade cables are available for use with the BMXDAO1605? Issue Product Line Modicon M340 Environment Cause Resolution For the BMXDAO1605, the only cabling option has a pigtail of wires on one end and a 20-way connector on the other end. Here are the available part numbers based on the length of the cable: BMXFTW301 - 3m BMXFTW501 - 5m BMXFTW1001 - 10m
Read more
There are two modes of events storage 1. Store All Events Here all the events are stored untill they reach the limit of storage which can be set by user. If still the events are coming they get lost. There is one option called \' Delete the oldest events \' if selected then the FIFO strategy is implemented in the event buffer. if this is not selected then the additional events are lost. 2. Store only recent events Here only the recent event for the data point is stored , so if ...
Read more
Yes, The left most slot of the rack is reserved for the power supply. The next slot is considered slot 0 and it is reserved for the CPU. The remaining slots numbered 1 - 11 (BMXXBP1200) can be used for I/O modules. Any module in any slot. Legacy KB System (APS) Data: RESL187213 V1.0, Originally authored by DaSo on 07/23/2007, Last Edited by DaSo on 07/23/2007 Related ranges: Modicon M340
Read more
No, there is not an alternative to the BMXXBP1200 that is DIN rail mountable. Due to mechanical considerations, it would not be easy to install and remove a rack of this size on DIN rail. Legacy KB System (APS) Data: RESL207557 V1.0, Originally authored by DaSo on 04/20/2012, Last Edited by DaSo on 04/20/2012 Related ranges: Modicon M340
Read more
a Greater than or equal to 60Â mm (2.36Â in.)
b Greater than or equal to 80Â mm (3.15Â in.)
1 Installation or casing
2 Wiring duct or tray
Dimensions in mm / in.
(1) The diameter of the fastening holes must allow use of M4, M5, M6 and UNCÂ #6 screws.
Rack | a | b | Size of the rack and extension module |
---|---|---|---|
BMXXBP040 and BMXXBP0400H | 207.8Â mm (8.187Â in.) | 242.2Â mm (9.543Â in.) | 243.4Â mm (9.59Â in.) |
BMXXBP0600 and BMXXBP0600H | 273Â mm (10.756Â in.) | 307.6Â mm (12.12Â in.) | 308.8Â mm (12.167Â in.) |
BMXXBP0800 and BMXXBP0800H | 338.2Â mm (13.325Â in.) | 372.8Â mm (14.69Â in.) | 374Â mm (14.736Â in.) |
BMXXBP1200 and BMXXBP1200H | 468.6Â mm (18.463Â in.) | 503.2Â mm (19.826Â in.) | 504.4Â mm (19.873Â in.) |
Fasten the rack with four M4, M5, M6 or UNCÂ #6 screws.