ATS48C11Q

$5,277.27
Generally ships in 1 to 2 days
SKU
ATS48C11Q

soft starter for asynchronous motor - ATS48 - 100 A - 230..415 V - 22..90 KW

Main
Range of product
Altistart 48
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Heavy duty industry and pumps
Device short name
ATS48
[Us] rated supply voltage
230...415 V (- 15...10 %)
Motor power kW
55 kW at 230 V (connection to the motor delta terminals) for standard applications

55 kW at 400 V (connection in the motor supply line) for standard applications

75 kW at 400 V (connection to the motor delta terminals) for severe applications

90 kW at 400 V (connection to the motor delta terminals) for standard applications

22 kW at 230 V (connection in the motor supply line) for severe applications

30 kW at 230 V (connection in the motor supply line) for standard applications

45 kW at 230 V (connection to the motor delta terminals) for severe applications

45 kW at 400 V (connection in the motor supply line) for severe applications
Power dissipation in W
For severe applications 252 W

For standard applications 322 W
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 5 In)
IcL starter rating
110 A (connection in the motor supply line) for severe applications

191 A (connection to the motor delta terminals) for severe applications

191 A (connection to the motor delta terminals) for standard applications

110 A (connection in the motor supply line) for standard applications
IP degree of protection
IP20
Complementary
Assembly style
With heat sink
Function available
External bypass (optional)
Supply voltage limits
195...456 V
Supply frequency
50...60 Hz (- 5...5 %)
Network frequency
47.5...63 Hz
Device connection
In the motor supply line

To the motor delta terminals
Factory setting current
100 A
[Uc] control circuit voltage
220 - 15 % to 415 + 10 %, 50/60 Hz
Control circuit consumption
30 W
Discrete output number
2
Discrete output type
(LO1) logic output 0 V common configurable

(LO2) logic output 0 V common configurable

(R1) relay outputs fault relay NO

(R2) relay outputs end of starting relay NO

(R3) relay outputs motor powered NO
Output absolute accuracy precision
+/- 5 %
Minimum switching current
Relay outputs 10 mA at 6 V DC
Maximum switching current
Logic output 0.2 A at 30 V DC

Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms

Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms
Discrete input number
5
Discrete input type
PTC, 750 Ohm at 25 °C

(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input voltage
24 V (<= 30 V)
Discrete input logic
Positive logic (Stop, Run, LI3, LI4) state 0 < 5 V and <= 2 mA, state 1 > 11 V and >= 5 mA
Supply inrush current
Adjustable 0.4...1.3 Icl
Analogue output type
(AO) current output 0-20 mA or 4-20 mA <= 500 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure (line)

Thermal protection (motor)

Thermal protection (starter)
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
290 mm
Width
190 mm
Depth
235 mm
Product weight
8.3 kg
Power range
15...25 kW at 200...240 V 3 phases

30...50 kW at 200...240 V 3 phases

30...50 kW at 380...440 V 3 phases

55...100 kW at 380...440 V 3 phases
Motor starter type
Soft starter
Environment
Electromagnetic compatibility
Conducted and radiated emissions conforming to IEC 60947-4-2 level A

Conducted and radiated emissions conforming to IEC 60947-4-2 level B

Damped oscillating waves conforming to IEC 61000-4-12 level 3

Electrostatic discharge conforming to IEC 61000-4-2 level 3

Immunity to electrical transients conforming to IEC 61000-4-4 level 4

Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3 level 3

Voltage/current impulse conforming to IEC 61000-4-5 level 3
Standards
EN/IEC 60947-4-2
Product certifications
CCC

CSA

C-Tick

DNV

GOST

NOM 117

SEPRO

TCF

UL
Vibration resistance
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6

1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level
58 dB
Pollution degree
Level 3 conforming to IEC 60664-1
Relative humidity
0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
40...60 °C with current derating of 2 % per °C

-10...40 °C without derating
Ambient air temperature for storage
-25...70 °C
Operating altitude
<= 1000 m without derating

> 1000...2000 m with current derating of 2.2 % per additional 100 m
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:ATS48C11Q

   Frequently Asked Questions and Answers


  • There is an application with Altivar 38 with pump switching card where the auxiliary pump is driven by an Altistart 48.There is also Modbus connection...

    Goals and Symptoms There is an application with Altivar 38 with pump switching card where the auxiliary pump is driven by an Altistart 48.There is also Modbus connection where the master is a Twido PLC and the slaves are the ATV38 and the ATS 48. The problem is that en error ERR 7 (erreur LS) is appeared at the ATV38 display.What kind of error is that and what can we do about it? Facts and Changes ATV38 with Modbus connection Causes and Fixes Product trips transiently to \'Err3\' or \'Err7\' fa...
    Read more

  • Can you run a single phase motor with an ATS22 or ATS48 softstart?

    Issue: Can you run a single phase motor with an ATS22 or ATS48 softstart? Product Line: Altistart 22, Altistart 48 Environment: All Cause: Single phase Resolution: No single phase option for this unit.
    Read more

  • What is a good source of information for the ATS48 soft start?

    Issue: Information is needed to facilitate installation and programming. Product line: Altistart ATS48 Environment: All models, all serial numbers Cause: None Resolution: Instruction Bulletin, S1A37491, includes information for installing and programming the ATS48. Instruction Bulletin, 30072-451-28, is a Maintenance and Repair manual. Use this URL to the Download Center: https://www.schneider-electric.com/en/product-range/689-altistart-48/
    Read more

  • Does the ATS22 use 24vdc control voltage?

    Issue: Does the ATS22 use 24vdc control voltage? Product Line: ATS22 Environment: All products of ATS22 Cause: N/A Resolution: The ATS22 do not use 24vdc control voltage externally. The ATS22...S6 series uses external 220Vac and the ATS22...S6U series uses 120Vac. Both have internal 24vdc (used to activate the logic inputs) but you would have to bring the appropriate control voltage to use the internal voltage.
    Read more

  • Where can I download SoMove software and the drive/soft starter DTM files?

    Issue: Where can I download SoMove software? Product Line: SoMove Software Environment: All Cause: Needs SoMove software and DTM files Resolution: Below are the Links for SoMove Software and DTMs for AC Drives and Softstarts. DTM files will need to be installed for drive profile recognition prior to connection through Somove.   SoMove core software: https://www.schneider-electric.us/en/download/document/SoMove_FDT/ DTM file for Altivar 600 series process drives         &nbsp...
    Read more

Software - Released
  • file image SoMove V2.6.5 (FDT Standalone) (exe) download image`
  • file image SoMove V2.6.5 (FDT Standalone) (pdf) download image`
User guide
  • file image ATS48 User manual (pdf) download image`
  • file image ATS48 Modbus manual (pdf) download image`
  • file image 1) ATS48 Getting started (pdf) download image`
  • file image ATS48 Getting Started Annex for UL508 (SCCR) (pdf) download image`
Catalogue
  • file image Catalog: Soft start/soft stop units Altistart 48 (pdf) download image`
CAD
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dwf) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dwg) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dxf) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (wmf) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dwf) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dwg) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (dxf) download image`
  • file image references ATS48D62Q, ATS48D75Q, ATS48D88Q, ATS48C11Q, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y (wmf) download image`
Certificate
  • file image ATS48_CSA_CERTIFICATE (pdf) download image`
  • file image E184727 UL GENERIC CERTIFICATES (pdf) download image`
  • file image ATV12 C-TICK CERTIFICATE (pdf) download image`
  • file image ATS48 C-TICK CERTIFICATE (pdf) download image`
  • file image ATS48 EU DECLARATION (pdf) download image`
End of life manual
  • file image Altistart 48 17 to 110 Amps - Standard applications, Product End-of-Life Instructions (pdf) download image`
Marine certificate
  • file image LR Marine Certificate ATS48 electronic soft starters (pdf) download image`
  • file image DNV-GL Marine Certificate Altistart ATS48 motor starters (PDF) download image`
Product environmental
  • file image Altistart 48 17 to 110 Amps - Standard applications, Product Environmental Profile (pdf) download image`

Dimensions Drawings

Dimensions

(1) Right View

(2) Front View



Mounting and Clearance

Clearance