The power phases that are controlled by Altistart 01 Soft-Starter are as follows: In N1 Range of Altistart 01 Soft-Starter only 1 Phase is controlled and that is L1, L2 and L3 are uncontrolled. In N2 Range of Altistart 01 Soft-Starter only 2 Phases are controlled and that is L2 and L3, L1 is uncontrolled.
Read more
Issue: Do the Altistart 01 soft-starters have any available spare parts? Product Line: Altistart 01 Environment: All serial numbers for Altistart 01 Cause: N/A Resolution: There are no spare parts available for the Altistart 01 soft-starters
Read more
Issue: What are the dimensions for the ATS01N230LY and ATS01N244LY? Product Line: Altistart 01 Environment: All Cause: N/A Resolution: Both units have the same dimensions: 4.96 (126 mm) inches deep 5.75 (146 mm) inches tall 7.09 (180 mm) inches wide
Read more
Issue: Does the ATS01 softstart require external thermal overload protection? Product Line: ATS01, Altistart 01 Environment: All Cause: N/A Resolution: The ATS01 softstart does require an external overload thermal protection for the motor. It also requires a starter or a contactor to be used at the line of the softstart.
Read more
Issue: Wants to order the ATS01N230LY, ATS01N244LY, ATS01N272LY or ATS01N285LY Product line: ATS01, Altistart 01, High HP Environment: All models Cause: The launch of the ATS22 in 2011 caused the High HP units to become redundant. Resolution: The ATS01 High HP units were replaced with the ATS22 units. These are functional replacements only. The ATS01 had no overload protection, an internal power supply and simple dial adjustments. The ATS22 will require external 120V or 230V po...