A9R21480

$416.41
Generally ships in 1 to 2 days
SKU
A9R21480

Acti 9 iID - RCCB - 4P - 80A - 30mA - type A

Main
Range
Acti 9
Product name
Acti 9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
IID
Poles description
4P
Neutral position
Left
[In] rated current
80 A
Network type
AC
Earth-leakage sensitivity
30 mA
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Complementary
Device location in system
Outgoer
Network frequency
50/60 Hz
[Ue] rated operational voltage
380...415 V AC 50/60 Hz
Residual current tripping technology
Voltage independent
Rated breaking and making capacity
Im 1500 A

Idm 1500 A
Rated conditional short-circuit current
10 kA
[Ui] rated insulation voltage
500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV
Contact position indicator
Yes
Control type
Toggle
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
8
Height
91 mm
Width
72 mm
Depth
73.5 mm
Product weight
0.37 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles AC-1
Locking options description
Padlocking device
Connections - terminals
Single terminal, top or bottom flexible with ferrule wire(s) 1...25 mm² max

Single terminal, top or bottom rigid wire(s) 1...35 mm² max

Single terminal, top or bottom flexible wire(s) 1...25 mm² max
Wire stripping length
14 mm (top or bottom)
Tightening torque
3.5 N.m (top or bottom)
Environment
Standards
EN/IEC 61008-1
IP degree of protection
IP40 for modular enclosure conforming to IEC 60529

IP20 conforming to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
Ambient air temperature for operation
-25...60 °C
Ambient air temperature for storage
-40...85 °C
Offer Sustainability
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
Need no specific recycling operations
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
Contractual warranty
Warranty period
18 months 18 months
Write Your Own Review
You're reviewing:A9R21480

   Frequently Asked Questions and Answers


  • What is the replacement for 16780?

    The replacement is A9R21480 A9R12480 iID - RCCB - 4P - 80A - 100mA - AC type For more information see: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9R12480
    Read more

  • Do we have an RCD Trip Curve for Acti 9 breakers?

    Schneider does not publish a trip curve for Acti 9 MCB. However, it is confirmed that they comply with the standards IEC 61008, IEC 61009 and AS/NZS3190:2002 Type II. The maximum break times for these standards are outlined in the document attached with advise on discrimination with RCD devices. Acti 9 Technical Catalogue RCD.pdf
    Read more

  • Does the Neutral require connection on a Acti 9 (4 pole) RCCB?

    Installation guide for RCCB for 3P without neutral If you are using Acti9 range RCCB, You don't need to add the resistor with iID Acti9 RCCB. You can directly connect the 3 phase on 3 poles of RCCB (without neutral).
    Read more

  • Are Acti 9 Busbars cuttable?

    Yes They can be cut. Please refer the following link ,showing the processor , how to cut it. https://se--c.na18.content.force.com/servlet/servlet.FileDownload?file=00PA000000DAz5j
    Read more

  • Is the Acti 9 a9mem3110 3 phase?

    Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.
    Read more

CAD
  • file image ACTI9 IID 4P (zip) download image`
  • file image ACTI9 IID 4P (pdf) download image`
  • file image ACTI9 IID 4P (stp) download image`
Certificate
  • file image CB Certificate ES2004 for iID Monoconnect and iIDK 4P according to IEC 61008-1 and IEC 61008-2-1 (pdf) download image`
  • file image Certificate of Approval (pdf) download image`
  • file image VDE Certificate for iID according to EN61008-1:2012 and EN 61008-2-1:1994 +A11:1998 (pdf) download image`
Declaration of conformity
  • file image EU Declaration FD16041418 for RCCB iID (pdf) download image`
Product environmental
  • file image Acti9-Residual current circuit breaker-iID - PEP (pdf) download image`
  • file image Product Environmental ProfileActi9 - Residual current circuit breaker -iID (pdf) download image`
REACh Declaration
  • file image Acti 9 iID - RCCB - 4P - 80A - 30mA - type A (pdf) download image`
RoHs Declaration
  • file image Acti 9 iID - RCCB - 4P - 80A - 30mA - type A (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech