A9F94310

$276.17
Special Order-Generally ships in 14 to 21 Business Days
SKU
A9F94310

iC60L - miniature circuit breaker - 3P - 10A - C curve

Main
Device application
Distribution
Range
Acti 9
Product name
Acti 9 iC60
Product or component type
Miniature circuit-breaker
Device short name
IC60L
Poles description
3P
Number of protected poles
3
[In] rated current
10 A
Network type
AC

DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
20 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz

25 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz

50 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz

70 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz

70 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz

15000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz

20 kA Icu conforming to EN/IEC 60947-2 - <= 180 V DC
Utilisation category
Category A conforming to EN 60947-2

Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to EN 60947-2

Yes conforming to IEC 60947-2

Yes conforming to EN 60898-1

Yes conforming to IEC 60898-1
Standards
EN 60898-1

EN 60947-2

IEC 60898-1

IEC 60947-2
Complementary
Network frequency
50/60 Hz
Magnetic tripping limit
8 x In +/- 20 %
[Ics] rated service breaking capacity
35 kA 50 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz

35 kA 50 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz

20 kA 100 % x Icu conforming to EN 60947-2 - 125...180 V DC

20 kA 100 % x Icu conforming to IEC 60947-2 - 125...180 V DC

7500 A 50 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz

7500 A 50 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz

25 kA 50 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz

12.5 kA 50 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz

10 kA 50 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz

25 kA 50 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz

12.5 kA 50 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz

10 kA 50 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz
Limitation class
3 conforming to EN 60898-1

3 conforming to IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to IEC 60947-2

500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2

6 kV conforming to IEC 60947-2
Contact position indicator
Yes
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Fixed
Mounting support
DIN rail
Comb busbar and distribution block compatibility
YES top or bottom
9 mm pitches
6
Height
85 mm
Width
54 mm
Depth
78.5 mm
Product weight
0.375 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal, top or bottom rigid wire(s) 1...25 mm² max

Single terminal, top or bottom flexible wire(s) 1...16 mm² max
Wire stripping length
14 mm top or bottom
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Environment
IP degree of protection
IP20 conforming to EN 60529

IP20 conforming to IEC 60529
Pollution degree
3 conforming to EN 60947-2

3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % ( 55 °C )
Operating altitude
0...2000 m
Ambient air temperature for operation
-35...70 °C
Ambient air temperature for storage
-40...85 °C
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Product Environmental Profile
Product end of life instructions
Need no specific recycling operations
Contractual warranty
Warranty period
18 months
Write Your Own Review
You're reviewing:A9F94310

   Frequently Asked Questions and Answers


  • ETSNZ - Are acti9 ic60 MCBs suitable for DC applications?

    Yes, Acti9 iC60N/H MCBs are suitable for DC applications ranging from 12VDC to 250VDC subject to the number of poles connected in series and the required breaking capacity. The attached document shows the number of poles that are required to be connected in series in relation to the supply voltage and the breaking capacity that is achieved.    Acti9_iC60.pdf
    Read more

  • What is the magnetic tripping threshold of the ic60 and older c60 circuit breakers used in DC network?

    The magnetic tripping threshold of the Acti 9 and older Multi 9 circuit breakers is higher than in alternating current. The magnetic tripping threshold is determined based on the attached documents. Acti 9.pdf Multi 9.JPG
    Read more

  • What is the 4 pole vigi unit that fits the Acti 9 ic60, 3 pole and 4 pole circuit breakers?

    The 4 pole Vigi unit is the A9V02763. See below for more information https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02763
    Read more

  • Is there a lock dog for ic60 RCBO?

    Yes, there is a padlocking device. The part number is  A9A27049 and it comes in lots of 10.  For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=A9A27049
    Read more

  • What is the part number for a 3 pole 32 amp D curve ic60 circuit breaker?

    Part number for a 3 pole 32 amp \'D\' curve Breaker in 10kA is....A9F55332 See link for more detail.... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55332
    Read more

CAD
  • file image ACTI9 IC60 3P (zip) download image`
  • file image ACTI9 IC60 3P (pdf) download image`
  • file image ACTI9 IC60 3P (stp) download image`
Certificate
  • file image Licence IMQ for MCB iC60L CA03.00666 according to EN 60947-2 (pdf) download image`
  • file image Licence IMQ for MCB iC60L CA03.00657 according to EN 60898-1:2003 +A1+A11+A12+A13 (pdf) download image`
  • file image CCA Certificate for MCB iC60H FR684357B according to EN 60947-2:2006 +A1 +A2 (pdf) download image`
  • file image CCA Certificate for MCB iC60L FR684357A according to EN 60898-1:2003 +A1+A11+A12+A13 (pdf) download image`
  • file image CB Certificate for MCB iC60L FR652076B M1 according to IEC 60947-2:2006 +A1 +A2 (pdf) download image`
  • file image CB Certificate for MCB iC60L FR682571B M1 according to IEC 60898-1:2002+A1+A2 (pdf) download image`
Declaration of conformity
  • file image EU Declaration FD16032918 iC60aNHL MCB (pdf) download image`
Product environmental
  • file image iC60 Circuit Breaker - PEP (pdf) download image`
REACh Declaration
  • file image iC60L - miniature circuit breaker - 3P - 10A - C curve (pdf) download image`
RoHs Declaration
  • file image iC60L - miniature circuit breaker - 3P - 10A - C curve (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech