A9D11806

$84.92
Generally ships in 1 to 2 days
SKU
A9D11806

iC60H - earth leakage circuit breaker - 1P + N - C curve - 6 A - 30m A - 240 V

Main
Circuit breaker application
Distribution
Range
Acti 9
Product name
Acti 9 iC60 RCBO
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
IC60H RCBO
Poles description
1P + N
[In] rated current
6 A at 50 °C
Earthing system
TN
Curve code
C
Earth-leakage sensitivity
30 mA
Breaking capacity
Icn : 10000 A - 240 V - AC at 50/60 Hz
Complementary
Neutral position
Left
Number of protected poles
1
Device location in system
Outgoer
Network type
AC
Network frequency
50 Hz
[Ue] rated operational voltage
Ue: 240 V - AC at 50/60 Hz
Trip unit technology
Thermal-magnetic
Residual current tripping technology
Voltage dependent
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity
Ics: 7500 A - 240 V - AC at 50/60 Hz
Limitation class
3
[Ui] rated insulation voltage
Ui: 400 V - AC at 50/60 Hz
[Uimp] rated impulse withstand voltage
Uimp: 4 kV
Suitability for isolation
Yes
Contact position indicator
Yes
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
NO
9 mm pitches
2
Height
110 mm
Width
18 mm
Depth
77.5 mm
Product weight
205 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles
Provision for padlocking
Padlockable with padlock Ø 4 mm
Locking options description
ON/OFF locking facilities
Connections - terminals
Screw clamp terminal connection on top - 1...25 mm² - rigid - without cable end

Screw clamp terminal connection on top - 1...16 mm² - flexible

Screw clamp terminal connection on bottom - 1...16 mm² - rigid - without cable end

Screw clamp terminal connection on bottom - 1...10 mm² - flexible
Wire stripping length
13 mm on bottom of power circuit

14 mm on top of power circuit
Tightening torque
3.5 N.m on top of power circuit

2 N.m on bottom of power circuit
Earth-leakage protection
Integrated
Environment
Standards
IEC 61009-1

BS EN 61009-1

IEC 61009-2-2

AS/NZS 61009.1
IP degree of protection
IP20
Tropicalisation
2
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-15...60 °C
Ambient air temperature for storage
-40...85 °C
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Schneider Electric declaration of conformity
REACh
Go to CaP for more details
Product environmental profile
Product Environmental Profile
Product end of life instructions
End of Life Information
Write Your Own Review
You're reviewing:A9D11806

   Frequently Asked Questions and Answers


  • Is there a lock dog for ic60 RCBO?

    Yes, there is a padlocking device. The part number is  A9A27049 and it comes in lots of 10.  For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=A9A27049
    Read more

  • What are the part numbers for Padlocking device which will go on LHS and RHS of Acti 9 ic60 and RCBO\'s?

    Part number A9A26380 is for mounting on the left side of Circuit Breaker. Part number A9A26381 is for mounting on the  Right side of Circuit breaker. For further details please follow the below link, https://www.tracepartsonline.net/(S(jj1xcpflpzf1tyxwjtna0vip))/partdetails.aspx?PartID=10-02112015-105620&class=SCHNEIDER_ELECTRIC_DISTRI&clsid=/SCHNEIDER_DISTRI/F_SCHNEIDER_DISTRI/SCHNEIDER_DISTRI.030/SCHNEIDER_DISTRI.030.010/
    Read more

  • How can I make 1 Pole 10 Amps B Curve 30ma RCBO?

    To make 1 Pole 10 Amps B Curve 30mA RCBO, you need the following: A9F53110 - 1 Pole 10 Amps B Curve Breaker (https://www.schneider-electric.com.au/en/search/A9F53110) + A9V02663 - 2 Pole 30mA 63 Amps Add-on Vigi to suit 1 Pole iC60 Breakers (https://www.schneider-electric.com.au/en/search/A9F53110) Please note the total width of this combination will be equal to 3 Poles standard RCBO (3 x 18mm)
    Read more

  • ETSNZ - Are acti9 ic60 MCBs suitable for DC applications?

    Yes, Acti9 iC60N/H MCBs are suitable for DC applications ranging from 12VDC to 250VDC subject to the number of poles connected in series and the required breaking capacity. The attached document shows the number of poles that are required to be connected in series in relation to the supply voltage and the breaking capacity that is achieved.    Acti9_iC60.pdf
    Read more

  • What is the magnetic tripping threshold of the ic60 and older c60 circuit breakers used in DC network?

    The magnetic tripping threshold of the Acti 9 and older Multi 9 circuit breakers is higher than in alternating current. The magnetic tripping threshold is determined based on the attached documents. Acti 9.pdf Multi 9.JPG
    Read more

Instruction sheet
  • file image iC60N - RCBO instruction sheet (pdf) download image`
CAD
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (dwf) download image`
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (dwg) download image`
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (dxf) download image`
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (wmf) download image`
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (pdf) download image`
  • file image iC60N-H RCBO 1P+N 6A…45A 30/100mA with overcurrent protection (stp) download image`
Certificate
  • file image CB Certificate SE-87253 for iC60N-H RCBO according to IEC 61009-1:2010 +A1 +A2 and IEC 61009-2-2:1991 (pdf) download image`
  • file image CB Test Certificate (pdf) download image`
  • file image Certificate of Approval (pdf) download image`
Declaration of conformity
  • file image EU Declaration FD16040504B for iC60N-H RCBO (pdf) download image`
End of life manual
  • file image iC60 RCBO - EoLi (pdf) download image`
Product environmental
  • file image iC 60 RCBO - PEP (pdf) download image`
REACh Declaration
  • file image iC60H - earth leakage circuit breaker - 1P + N - C curve - 6 A - 30m A - 240 V (pdf) download image`
RoHs Declaration
  • file image iC60H - earth leakage circuit breaker - 1P + N - C curve - 6 A - 30m A - 240 V (pdf) download image`
© 2018 Switchboard in a Box. All Rights Reserved. Design & Developed by Shaligram Infotech